background image

Rev. 0508 

7

Electrical Service Receptacles (When Applicable)

The receptacles located on the exterior of the merchandiser 

are intended for scales and lighted displays. They are not 

intended  nor  suitable  for  large  motors  or  other  external 

appliances.

BEFORE SERVICING

ALWAYS DISCONNECT ELECTRICAL

POWER AT THE MAIN DISCONNECT

WHEN SERVICING OR REPLACING ANY

ELECTRICAL COMPONENT.

This includes (but not limited to) Fans, Heaters

Thermostats, and Lights.

Field Wiring and Serial plate Amperage

Field Wiring must be sized for component amperes printed 

on the serial plate. Actual ampere draw may be less than 

specified. Field wiring from the refrigeration control panel to 

the merchandisers is required for refrigeration thermostats. 

Most component amperes are listed in the “Case Specs” 

section, but always check the serial plate.

Ballast Location

Ballasts are located within the access panel that runs the 

length of the rear of the case. Refer to diagram on page 6.
 

 

Electrical

Wiring Color Code

CASE MUST BE GROUNDED

NOTE:   Refer to label illustrated above that is affixed to case 

to determine the actual configuration as checked in the 

“TYpE INSTALLED” boxes.

Electrical Circuit Identification

Standard lighting for all models will be full length fluorescent 

lamps located within the case at the top.
The  switch  controlling  the  lights,  the  plug  provided  for 

digital scale, and the thermometer are located at the rear 

of the case mullion.
The receptacle that is provided on the exterior back of these 

models is intended for computerized scales with a five amp 

maximum load, not for large motors or other high wattage 

appliances. It should be wired to a dedicated circuit.

Finishing Touches

plexiglass Joining Instructions

Note: 

All cases in a line up are set, leveled and joined together 

in the factory to ensure proper alignment and tight joints 

between the cases. To obtain equally tight joints between 

cases, it is critical to use the GE 1200 silicone (supplied 

with cases) for sealing case joints. Only the use of 

silicone allows case joints to pull up tight! DO NOT USE 

pERMAGUM! Use of permagum will cause large gaps at 

case joints.

parts List

•   1” Plastic rod 3/16” diameter

•   Acrylic Solvent Cement (IPS weldon #40 or 

comparable)

•   Masking tape and duct tape (not supplied)

Instructions

1.   Prepare front plexiglass for cement application by 

placing masking tape, a maximum 1/16 of an inch 

from the seam, on both sides front and back. Tape is 

to protect plexiglass from cement spill over. Scarring 

will occur if cement touches clear plexiglass.

.   Separate front plexiglass pieces enough to apply a 

bead of #40 cement down one edge inside of seam 

and plastic rod area.

3.   Realign front plexiglass and push together tightly. 

Insert the plastic rod until flush with top of plexiglass.

4.   Apply tape (” duct tape recommended) across 

face of seam to secure plexiglass from shifting while 

cement dries (approximately 1 hour).

5.   With a little silicone, attach the plex clip over the joint 

in the glass.

Weldon #40 (2-part) Cement - Mixing Instructions

1.   Bring Parts “A” and “B” to room temperature before 

mixing.

.  Add Part “A” to Part “B”. They have been 

premeasured at the factory.

3.   Stir slowly and evenly, as to avoid air bubbles. Mix for 

1-3 minutes.

Summary of Contents for CHINO CID

Page 1: ...CID ISLAND CHEESE DELI CASE p n IGIC CID 0508 INSTALLATION OPERATION GUIDE CHINO CID ISLAND CHEESE DELI CASE Rev 0508 Installation Operation Manual...

Page 2: ...Self Service Island Display including 5 and 6 Crowns and 4 Center Modules available as standard refrigerated med low temp and hot Shipping Damage All equipment should be thoroughly examined for shipp...

Page 3: ...Rev 0508 Cut and Plan Views...

Page 4: ...he store floor B When wedges are involved in a lineup set them first All cases were leveled and joined prior to shipment to insure the closest possible fit when cases are joined in the field When join...

Page 5: ...nd product losses Please follow the recommendations listed below when installing condensate drains to insure a proper installation 1 Never use pipe for condensate drains smaller than the nominal diame...

Page 6: ...case setup the connecting point in the store may be 5 8 7 8 or 11 8 Refer to the particular case you are hooking up Refrigerant lines should be sized as shown on the refrigeration legend furnished by...

Page 7: ...ntended for computerized scales with a five amp maximum load not for large motors or other high wattage appliances It should be wired to a dedicated circuit Finishing Touches Plexiglass Joining Instru...

Page 8: ...d product life at the factory The use of higher output fluorescent lamps H O and V H O will shorten the shelf life of the product Case Cleaning Long life and satisfactory performance of any equipment...

Page 9: ...very effective in not only cleaning and polishing the Plexiglass surface but also providing anti static and anti fog capabilities This product also seals pores and provides a protective coating Insta...

Page 10: ...Check fixture loading Overstocking case will affect its proper operation 3 If frost is collecting on fixture and or product check that Humidity Control is working properly and that no outside doors or...

Page 11: ...120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L CAP UNUSED RED LEAD LIGHT SWITCH BUNDLE COLOR...

Page 12: ...AM LH3 120 L CAP UNUSED RED LEAD LIGHT SWITCH BUNDLE COLOR ORANGE 115 VAC 50 60 Hz M M M 115 VAC 50 60 Hz BUNDLE COLOR BROWN 115 VAC 50 60 Hz BUNDLE COLOR BLACK WHITE EVAPORATOR FAN MOTORS 3 GE 9 W 11...

Page 13: ...25 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L LIGHT SWITCH BUNDLE COLOR ORANGE 115 VAC 50 60 Hz 115 VAC 50 60 Hz BUNDLE COLOR BROWN 115 VAC 50 60 Hz BUNDLE COLOR BLACK WHITE EVAPORA...

Page 14: ...ST 125 01 3266 FULHAM LH3 120 L LIGHT SWITCH BUNDLE COLOR ORANGE 115 VAC 50 60 Hz 115 VAC 50 60 Hz BUNDLE COLOR BROWN 115 VAC 50 60 Hz BUNDLE COLOR BLACK WHITE EVAPORATOR FAN MOTOR 1 GE 9 W 115 VAC SU...

Page 15: ...z M M M 115 VAC 50 60 Hz BUNDLE COLOR BROWN 115 VAC 50 60 Hz BUNDLE COLOR BLACK WHITE EVAPORATOR FAN MOTORS 3 GE 9 W 115 VAC SUCTION SOLENOID OPTIONAL T STAT OPTIONAL BALLAST 125 01 3266 FULHAM LH3 12...

Page 16: ...les and Hot Wells b Observation of outside influences such as drafts radiant heating from the ceiling and from lamps Such influence should be properly corrected or compensated for c Complete start up...

Page 17: ...e opening c READING It should first be determined that the refrigerator is refrigerating and has operated at least one hour since the end of the last defrost period The thermometer reading should be m...

Page 18: ...rea s Cleaning practices particularly with respect to proper refrigerator unloading and warm up must be in accordance with applicable recommendations 1 1 Cleaning of non frozen food equipment should i...

Page 19: ...e cleaning of equipment within the compartment and the hot area s Cleaning practices particularly with respect to proper refrigerator unloading and warm up must be in accordance with applicable recomm...

Page 20: ..._________________________________ _______________ ___________________________________________________________________________________________________ _______________ __________________________________...

Reviews: