Rev. 0508
3
Sporland Omnistat Time Clock program Settings
LIST OF pARAMeTeRS
Display parameter
Type Min Max Unit Default
value
CIDM
pS
pASSWORD
F
0 199
-
22
/
pROBe pARAMeTeRS
/C
ambient probe calibration (x 0.1°C/°F)
F -17 17 °C/°F 0.0
0.0
/
Measurement stability
C
1
15
-
4
4
/4
probe display: 0 = regulation probe, 1 = product food probe (second probe)
C
0
1
flag
0
1
/5
°C/°F (0=°C, 1=°F)
C
0
1
flag
0
1
r
ReGULATOR pARAMeTeRS
rd
Regulating differential (hysteresis 0=0.5 °C/ °F)
F
0
19 °C/°F
8
r1
Minimum allowable set
C
-50 r °C/°F -50
26°F
r
Maximum allowable set Cr1 17 °C/°F 60
C
r1 17 °C/°F
60
32°F
r3
Enabling Ed alarm: max duration of defrost is reached (0 = no, 1 = yes)
C
0
1
flag
0
0
r4
Automatic variation of the Set-Point with closed curtain-switch (A4=4)
C
-0 0 °C/°F
3
nU*
c
COMpReSSOR pARAMeTeRS
c0
Delay in the compressor start-up after switch-on
C
0
15 min
0
1
c1
Minimum time between two following compressor start-ups
C
0
15 min
0
1
c
Compressor shutdown minimum time
C
0
15 min
0
1
c3
Compressor operation minimum time
C
0
15 min
0
2
c4
Safety compressor (0 = OFF, 100 = ON)
C
0 100 min
0
10
cc
Continuous cycle duration
C
0
15 hours
4
2
c6
Alarm delay after continuous cycle
C
0
15 hours
6
d
DeFROST pARAMeTeRS
d0
defrost type (0 = heater, 1 = hot gas, = time resistance, 3 = time hot gas)
C
0
3
flag
0
2
d1
Time interval between two defrost cycles
F
0 199 hours
8
4
dt
End defrost temperature
F
-50 17 °C/°F
4
60
dP
Max defrost duration or effective duration if d0= or 3
F
1 199 min
30
25
d4
Defrost after start-up (0 = no, 1 = yes)
C
0
1
flag
0
0
d5
Delay defrost after control Switch-On or from digital input (A4 or A5=4)
C
0 199 min
0
0
d6
Block temperature display during defrost (0 = no, 1 = yes)
C
0
1
flag
1
1
dd
Dripping time after defrost
F
0
15 min
0
d8
Alarm delay after defrost
F
0
15 hours
1
2
d9
defrost priority over compressor protection (0 = no, 1 = yes)
C
0
1
flag
0
0
d/
Temperature defrost probe display
F
-
- °C/°F
-
-
dC
Time base (0=hours/min, 1=min/s) Only for dl and dP
C
0
1
flag
0
0
A
ALARM pARAMeTeRS
A0
Alarms and fans differential (0=0.5 °C/°F)
C
0
19 °C/°F
0
0
AL
Low temperature alarm (max. variation as to the Set-Point). AL=0 excluded Low temperature alarm
F
0 17 °C/°F
0
0
AH
High temperature alarm (max. variation as to the Set-Point). AH=0 excluded High temperature alarm F
0 17 °C/°F
0
0
Ad
Temperature alarm delay
C
0 199 min
0
0
A7
Measurement delay time for the input “delayed alarm” (A4 or A5=)
C
0 199 min
0
nU*
F
FAn pARAMeTeRS
F0
Management of fans: 0=fans ON, specific phases excluded (F2, F3 and Fd) 1 = fans ON (dependent
on parameter F1) specific phases excluded
C
0
1
flag
0
n/A
F1
Fan power on temperature
F
-50 17 °C/°F
5
n/A
F
Fans OFF when the compressor is OFF (0 = no, 1 = yes)
C
0
1
flag
1
n/A
F3
Fans OFF during defrost (0 = no, 1 = yes)
C
0
1
flag
1
n/A
Fd
Stop after dripping ON for each F0 value
F
0
15 min
1
n/A
H
OTHeR SeLeCTIOnS
H0
Serial address
C
0 199
-
1
1
H1
Selection of the alarm relay operation 0=alarm ON, energized relay, 1= alarm ON, disenergized relay
C
0
1
flag
1
1
H
0=disabled buttons, 1=enabled buttons
C
0
1
flag
1
0
H5
Identification code for programming key (programmed by supervisor)
F
-99 199
-
-
-
T
External parameter programming
C
-99 99
-
0
0
*show the set value
NU*: not used parameter, leave the default value
please contact Sporlan valve Company for further information. www.sporIan.com