Appendix A. - Temperature Guidelines - Refrigerated

The  refrigerators  should  be  operated  according  to  the 

manufacturer’s  published  engineering  specifications  for 

entering air temperatures for specific equipment applications. 

Table 1 shows the typical temperature of the air entering the 

food zone one hour before the start of defrost and one hour 

after defrost for various categories of refrigerators. Refer to 

Appendix C for Field Evaluation Guidelines.

Table

Type of Refrigerator

Typical entering 

Air Temperature

I.  OPEN DISPLAY

  A.  Non frozen:

    1)  Meat

8°F

    )  Dairy/Deli

3°F

    3)  Produce

      a. Processed

36°F

      b. Unprocessed

45°F

  B.  Frozen

0°F

  C.  Ice Cream

-5°F

II. CLOSED DISPLAY

  A.  Non frozen:

    1)  Meat

34°F

    )  Dairy/Deli

34°F

    3)  Produce

      a. Processed

36°F

      b. Unprocessed

45°F

  B.  Frozen

0°F

  C.  Ice Cream

-5°F

       Single Deck                Multi Deck           Service Case   Reach-In 
       

I. Open Display Styles

                         

II. Closed Display Styles

Hot

1.0  Hot cases are tested to maintain all hot food at 140° 

- 150°F. These cases are not designed to heat up or 

cook food. It is the user’s responsibility to stock the hot 

food cases immediately after the cooking of the food 

with a pulp temperature of at least 150° to 160°F.

Appendix B. - Application Recommendations - 

Refrigerated

1.0  Temperature performance is critical for controlling 

bacteria growth. Therefore, the following 

recommendations are included in the standard. 

They are based on confirmed field experience 

over many years.

1.1  The installer is responsible for following the 

installation instructions and recommendations 

provided by Hussmann for the installation 

 

of each individual type refrigerator.

1.  Refrigeration piping should be sized according to 

the equipment manufacturer’s recommendations 

and installed in accordance with normal refrigeration 

practices. Refrigeration piping should be insulated 

according to Hussmann’s recommendations.

1.3  A clogged waste outlet blocks refrigeration. The 

installer is responsible for the proper installation 

of the system which dispenses condensate waste 

through an air gap into the building indirect waste 

system.

1.4  The installer should perform a complete start-up 

evaluation prior to the loading of food into the 

refrigerator, which includes such items as: 

a)  Initial temperature performance, Coils should 

be properly fed with a refrigerant according to 

manufacturer’s recommendations.

b)  Observation of outside influences such 

as drafts, radiant heating from the ceiling 

and from lamps. Such influence should be 

properly corrected or compensated for. 

c)  At the same time, checks should be made of 

the store dry-bulb and wet-bulb temperatures 

to ascertain that they are within the limits 

prescribed by Hussmann.

d)  Complete start-up procedures should include 

checking through a defrost to make certain 

of its adequate frequency and length without 

substantially exceeding the actual needs. 

This should include checking the electrical 

or refrigerant circuits to make sure that 

defrosts are correctly programmed for all the 

refrigerators connected to each refrigeration 

system. 

e)  Recording instruments should be used to 

check performance.

Hot Food

1.0  The installer should perform a complete start-up 

evaluation prior to the loading of food into the hot 

food case, which includes such items as:

a)  Initial temperature performance, Griddles and 

Hot Wells.

b)  Observation of outside influences such 

as drafts, radiant heating from the ceiling 

and from lamps. Such influence should be 

properly corrected or compensated for.

c)  Complete start-up procedures should include:

  1. Heat / display lamps are lighting

  . Indicator lamps on control panel(s) are working

  3. Auto-fill is functioning properly (Service cases)

  4. Hot Griddles are functioning.

Summary of Contents for CHINO CIDM-E

Page 1: ...CIDM E CIDM I p n IGIC CIDM 0508 INSTALLATION OPERATION GUIDE CHINO CIDM E I Rev 0508 Installation Operation Manual...

Page 2: ...ains Information on CIDME CIDMI Refrigerated Self Service Island Display including 4 Crown and 3 Center Modules available as standard refrigerated med temp Shipping Damage All equipment should be thor...

Page 3: ...Plan Views 29 1 2 6 9 19 5 16 6 3 16 2 7 8 11 3 11 16 40 13 16 48 3 16 CIDM ISLAND 3 11 16 CIDME 34 7 8 3 1 16 12 13 16 27 36 33 30 3 8 10 Elec Elec Elec Ref 26 1 8 25 1 8 23 1 16 21 1 8 23 1 8 Ref D...

Page 4: ...hen cases are joined in the field When joining use a carpenters level and shim legs accordingly Case must be raised correctly under legs where support is best to prevent damage to case 1 Check level o...

Page 5: ...and product losses Please follow the recommendations listed below when installing condensate drains to insure a proper installation 1 Never use pipe for condensate drains smaller than the nominal dia...

Page 6: ...Access to TX Valves and Drain Lines Mechanical Remove product from end of case Remove product racks Remove refrigeration and drain access panels labeled TX valve mechanical only and drain are located...

Page 7: ...s provided on the exterior back of these models is intended for computerized scales with a five amp maximum load not for large motors or other high wattage Finishing Touches Plexiglass Joining Instruc...

Page 8: ...V H O will shorten the shelf life of the product Case Cleaning Long life and satisfactory performance of any equipment are dependent upon the care given to it To insure long life proper sanitation an...

Page 9: ...ocated on the case itself CLEANING PRECAUTIONS When cleaning Do not use high pressure water hoses Do not introduce water faster than waste outlet can drain NEVER ONASELF CONTAINED UNIT WITHAN EVAPORAT...

Page 10: ...DM CIDME 4 X3 W0300006 CIDME w OMNISTAT W0300008 CIDMI 3 W0300007 CIDMI 3 w OMNISTAT W0300009 CIDM I R 14 W0300017 CIDM I SC 14 W0300018 CIDM I R Hot Gas 14 W0300019 CIDM I R Hot Gas 10 W0300020 CIDM...

Page 11: ...FAN H4 H2 H3 H1 L2 ZONE SENSOR IS LOCATED BEHIND THE TOP FRONT DISCHARGE AND IS ATTACHED TO THE FRONT CAD SUPPORT STANDARD EVAP SENSOR IS LOCATED ON THE SECOND RUN OF THE COIL COMING AWAY FROM THE CAD...

Page 12: ...OMNI STAT PN952911 230VAC POWER SUPPLY 230 Vac PROD TEMP AIR TEMP L 9 1 2 3 4 5 6 7 8 CONDENSING UNITS COPELAND F9AM A103 CFV 140 1 H P R 22 RLA 9 5 1857W MCC 13 7 LRA 43 3 225 03 0121 1 R CONDENSING...

Page 13: ...T8 SPX30 2 125 03 1072 F25 T8 SPX30 2 125 03 1072 208 240 VAC 60 Hz L1 ZONE EVAP DEF COMM COMP ALARM FAN H4 H2 H3 H1 L2 ZONE SENSOR IS LOCATED BEHIND THE TOP FRONT DISCHARGE AND IS ATTACHED TO THE FRO...

Page 14: ...MCC 13 7 LRA 43 3 225 03 0121 1 R CONDENSING UNIT M M LIGHT CIRCUIT 93A 100W M CRTL PRSR DUAL 225 01 0706B BLK 14 RED 14 WHT 14 WHT 14 RED 14 BLK 14 RED 14 MCA 7 8A MOP 15A SAFETY SWITCH FLOAT SWITCH...

Page 15: ...2 F25 T8 SPX30 2 125 03 1072 F25 T8 SPX30 2 125 03 1072 F25 T8 SPX30 2 125 03 1072 M M M EVAP FAN MOTORS 2 9W CW 125 01 3076 TERMINAL BLOCK 125 01 0295 BLUE WHITE 115 V L1 2 6 L2 L3 208 V 17 5 17 5 24...

Page 16: ...W BROWN BROWN CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE WHITE BLACK BROWN BROWN BROWN BROWN YELLOW YELLOW RED RED BLUE WHITE BLUE WHITE BLUE BLUE BALLAST 125 01 3273 MAGNETE B432PUNVHP A BAL...

Page 17: ...B432PUNVHP A BLUE BLUE BLUE WHITE BLUE WHITE RED RED YELLOW YELLOW BROWN BROWN BROWN BROWN BLACK WHITE F15 T8 SPX30 2 125 03 0007 F15 T8 SPX30 2 125 03 0007 F15 T8 SPX30 2 125 03 0007 F15 T8 SPX30 2 1...

Page 18: ...W BROWN BROWN CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE CAP OFF WIRE WHITE BLACK BROWN BROWN BROWN BROWN YELLOW YELLOW RED RED BLUE WHITE BLUE WHITE BLUE BLUE BALLAST 125 01 3273 MAGNETE B432PUNVHP A BAL...

Page 19: ...F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F17T8 24 125 03 1071 F32T8 48 125 03 1073 F32T8 48 1...

Page 20: ...5 03 1073 M M M 15 AMP FUSE 125 01 3282 FUSE HOLDER 125 01 3283 15 AMP FUSE 125 01 3282 FUSE HOLDER 125 01 3283 BLACK WHITE M FAN MOTORS 4 9W CW 00001212 F15T8 18 125 03 1075 F15T8 18 125 03 1075 F15T...

Page 21: ...18 07 CIDM W0300021 CIDM E R EVAP FAN MOTORS 2 125 01 0615A 6A 49W 120VAC LIGHT SWITCH TOGGLE 125 01 0307 INSIDE PERIMETER LIGHTS 2 125 03 1075 F15 T8 SPX30 OUTSIDE PERIMETER LIGHTS 4 125 03 1071 F17...

Page 22: ...MCA 65A MOP 15A L1 N BLK 14 WHT 14 TAG ORANGE BLK 14 WHT 14 TAG BROWN BALLAST 125 01 3266 FULHAM LH3 120 L INCOMING POWER 120 VAC 60 Hz GFCI DUPLEX 125 01 3178 BLK NOTE FOR GFCI PROTECTION IF MORE THA...

Page 23: ...t after control Switch On or from digital input A4 or A5 4 C 0 199 min 0 0 d6 Block temperature display during defrost 0 no 1 yes C 0 1 flag 1 1 dd Dripping time after defrost F 0 15 min 2 0 d8 Alarm...

Page 24: ...POINT desired temperature value Press the SET button for one second to display the Set Point value After few seconds the set value blinks Press UP or DOWN to increase or decrease the set point value p...

Page 25: ...with normal refrigeration practices Refrigeration piping should be insulated according to Hussmann s recommendations 1 3 A clogged waste outlet blocks refrigeration The installer is responsible for th...

Page 26: ...arge opening c READING It should first be determined that the refrigerator is refrigerating and has operated at least one hour since the end of the last defrost period The thermometer reading should b...

Page 27: ...hese rules a Buy quality products b Receive perishables from transit equipment at the ideal temperature for the particular product c Expedite perishables to the store s storage equipment to avoid unne...

Page 28: ...________________________________ _______________ ___________________________________________________________________________________________________ _______________ ___________________________________...

Reviews: