background image

iGiC-ism-0608

8

Plumbing

Waste Outlet and P-TRaP

The waste outlet is located off the center of the case on 

one side allowing drip piping to be run lengthwise under 

the fixture.

A  1-1/"  P-TRAP  and  thread  adapter  are  supplied  with 

each fixture. The P-TRAP must be installed to prevent air 

leakage and insect entrance into the fixture.

nOTe:   PvC-dWv solvent cement is recommended. Follow the 

manufacturer’s instructions.

installing Condensate drain

Poorly  or  improperly  installed  condensate  drains  can 

seriously interfere with the operation of this refrigerator, and 

result in costly maintenance and product losses. Please 

follow the recommendations listed below when installing 

condensate drains to insure a proper installation:

1.   Never use pipe for condensate drains smaller 

than the nominal diameter of the pipe or P-TRAP 

supplied with the case.

.   When connecting condensate drains, the P-TRAP 

must be used as part of the condensate drain 

to prevent air leakage or insect entrance. Store 

plumbing system floor drains should be at least 14" 

off the center of the case to allow use of the P-TRAP 

pipe section. Never use two water seals in series in 

any one line. Double P-TRAPS in series will cause a 

lock and prevent draining.

3.   Always provide as much down hill slope ("fall") as 

possible; 1/8" per foot is the preferred minimum. 

PVC pipe, when used, must be supported to 

maintain the 1/8" pitch and to prevent warping.

4.   Avoid long runs of condensate drains. Long runs 

make it impossible to provide the "fall" necessary for 

good drainage.

5.   Provide a suitable air break between the flood rim of 

the floor drain and outlet of condensate drain. 1" is 

ideal.

6.   Prevent condensate drains from freezing:

a. Do not install condensate drains in contact with 

non-insulated suction lines. Suction lines should 

be insulated with a non absorbent insulation 

material such as Armstrong's Armaflex.

b. Where condensate drains are located in dead 

air spaces (between refrigerators or between a 

refrigerator and a wall), provide means to prevent 

freezing. The water seal should be insulated to 

prevent condensation.

Refrigeration

Refrigerant Type

The  standard  refrigerant  will  be  R-404A  or  R  unless 

otherwise specified on the customer order. Check the serial 

plate on the case for information. Minimum opening for self 

contained condenser units - 150 sq. inch up to 1-1/ hp, 

00 sq. inch for over 1-1/hp.

Refrigeration lines

Liquid 

Suction

3/8” O.D.

5/8” O.D. 

nOTe:   The standard coil is piped at 

5

/

8

” (suction); however, 

the store tie-in may vary depending on the number of 

coils and the draw the case has. depending on the case 

setup, the connecting point in the store may be 

5

/

8

”, 

7

/

8

”, 

or 1

1

/

8

”. Refer to the particular case you are hooking up.

Refrigerant  lines  should  be  sized  as  shown  on  the 

refrigeration legend furnished by the store.
Install 

P-TRaPs

 (oil traps) at the base of all suction line 

vertical risers.

Pressure drop

 can rob the system of capacity. To keep the 

pressure drop to a minimum, keep refrigerant line run as 

short as possible, using the minimum number of elbows. 

Where elbows are required, use long radius elbows only.

Control settings

See ISM technical data sheet for the appropriate settings for 

your merchandiser. Maintain these parameters to achieve 

near constant product temperatures. Product temperature 

should be measured first thing in the morning, after having 

been refrigerated overnight. Defrost times should be as 

follows: OFF CYCLE - Defrost times should be as directed 

in the ISM technical data sheet. The number of defrosts per 

day and the duration of the defrost cycle may be adjusted 

to meet conditions present at your location.

access to TX valves and drain lines

mechanical -

 Remove product from end of case. Remove 

product  racks.  Remove  refrigeration  and  drain  access 

panels (labeled). TX valve (mechanical only) and drain are 

located under each access panel at end of the case.

electronic - 

The Electronic Expansion valve master and 

slave cylinder(s) are located within the electrical access 

panel(s).

electronic expansion valve (Optional)

A  wide  variety  of  electronic  expansion  valves  and  case 

controllers  can  be  utilized.  Please  refer  to  EEV  and 

controller  manufacturers  information  sheet.  Sensors  for 

electronic expansion valves will be installed on the coil inlet, 

coil outlet, and in the discharge air. (Some supermarkets 

require a 4th sensor in the return air). Case controllers will 

be located in the electrical raceway or under the case.

Summary of Contents for Chino ISM

Page 1: ...ISM CHeese deli island case P N IGic ism 0608 INSTALLATION OPERATION GUIDE CHINO ISM island cheese deli case Rev 0608 Installation Operation Manual...

Page 2: ...ed Mini Island Display Shipping Damage All equipment should be thoroughly examined for shipping damage before and during unloading This equipment has been carefully inspected at our factory and the ca...

Page 3: ...e to its permanent position as possible Remove the top of the crate Detach the walls from each other and remove from the skid Unbolt the case from the skid The fixture can now be lifted off the crate...

Page 4: ...e hand pull the bumper toward you with the other to open the inside lips Slowly apply pressure by rolling the bumper into the track 1 Check level of floor where cases are to be set Determine the highe...

Page 5: ...hat vinyl legs are positioned within the base grooves Roll vinyl top over full length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid T...

Page 6: ...yl top over full length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the Rigid Top over the Rigid Base 3 If necessary wipe clean with any hous...

Page 7: ...p so that vinyl legs are positioned within the base grooves Roll vinyl top over full length of base then tap with rubber mallet to ensure vinyl is securely locked into the base 2b Rigid Top Snap the R...

Page 8: ...ype The standard refrigerant will be R 404A or R22 unless otherwise specified on the customer order Check the serial plate on the case for information Minimum opening for self contained condenser unit...

Page 9: ...suction pressure with an accurate pressure gauge at the evaporator outlet 2 From a refrigerant pressure temperature chart determine the saturation temperature at the observed suction pressure 3 Measur...

Page 10: ...suitable for large motors or other external appliances BEFORE SERVICING ALWAYS DISCONNECT ELECTRICAL POWER AT THE MAIN DISCONNECT WHEN SERVICING OR REPLACING ANY ELECTRICAL COMPONENT This includes but...

Page 11: ...eria which will thrive in a deli department NOTE Soap and hot water are not enough to kill this bacteria A sanitizing solution must be included with each cleaning process to eliminate this bacteria SH...

Page 12: ...Attachment Plugs to completely De energize unit Failure to disconnect both plugsmay result in damage to equipment serious personal injury This includes but not limited to Fans Heaters Thermostats and...

Page 13: ...CORD EVAPORATOR FANS 2 00001212 12W 14A 120VAC EMB PAPST 9906 TERMINAL BLOCK 125 01 0295 BIRMINGHAM 860112 600W 5 0A 120 VAC 00007274 PRESSURE SAFETY POWER SWITCH 125 01 0271 L1 N G NEMA 5 15P POWER C...

Page 14: ...PORATOR FANS 2 00001212 EMB PAPST 9906 M M TERMINAL BLOCK 125 01 0295 BRIMHAM 860112 600W 115 VAC 00007274 PRESSURE SAFETY DEFROST TIMER PARAGON ERC 2 120 240V 50 60 Hz 125 01 0722 POWER SWITCH 125 01...

Page 15: ...ld perform a complete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a refriger...

Page 16: ...ith warm product 2 Is the product loaded beyond the Safe Load Line markers 3 Are the return air ducts blocked 4 Are the entering air ducts blocked 5 Is a dumped display causing turbulent air flow and...

Page 17: ...rm up and prolonged temperature recovery Food store refrigerators are not food chillers nor can they reclaim quality lost through previous mishandling d Care must be taken when cross merchandising pro...

Page 18: ..._________________________________ _______________ ___________________________________________________________________________________________________ _______________ __________________________________...

Reviews: