Appendix A. - Temperature Guidelines - Refrigerated

The  refrigerators  should  be  operated  according  to  the 

manufacturer’s  published  engineering  specifications  for 

entering air temperatures for specific equipment applications. 

Table 1 shows the typical temperature of the air entering the 

food zone one hour before the start of defrost and one hour 

after defrost for various categories of refrigerators. Refer to 

Appendix C for Field Evaluation Guidelines.

Table

Type of Refrigerator

Typical entering 

Air Temperature

I.  OPEN DISPLAY

  A.  Non frozen:

    1)  Meat

28°F

    2)  Dairy/Deli

32°F

    3)  Produce

      a. Processed

36°F

      b. Unprocessed

45°F

  B.  Frozen

0°F

  C.  Ice Cream

-5°F

II. CLOSED DISPLAY

  A.  Non frozen:

    1)  Meat

34°F

    2)  Dairy/Deli

34°F

    3)  Produce

      a. Processed

36°F

      b. Unprocessed

45°F

  B.  Frozen

0°F

  C.  Ice Cream

-5°F

       Single Deck                Multi Deck           Service Case   Reach-In 
       

I. Open Display Styles

                         

II. Closed Display Styles

Appendix B. - Application Recommendations - 

Refrigerated

1.0  Temperature performance is critical for controlling 

bacteria growth. Therefore, the following 

recommendations are included in the standard. 

They are based on confirmed field experience 

over many years.

1.1  The installer is responsible for following the 

installation instructions and recommendations 

provided by Hussmann for the installation 

 

of each individual type refrigerator.

1.2  Refrigeration piping should be sized according to 

the equipment manufacturer’s recommendations 

and installed in accordance with normal 

refrigeration practices. Refrigeration piping 

should be insulated according to Hussmann’s 

recommendations.

1.3  A clogged waste outlet blocks refrigeration. The 

installer is responsible for the proper installation 

of the system which dispenses condensate waste 

through an air gap into the building indirect waste 

system.

1.4  The installer should perform a complete start-up 

evaluation prior to the loading of food into the 

refrigerator, which includes such items as: 

a)  Initial temperature performance, Coils should 

be properly fed with a refrigerant according to 

manufacturer’s recommendations.

b)  Observation of outside influences such 

as drafts, radiant heating from the ceiling 

and from lamps. Such influence should be 

properly corrected or compensated for. 

c)  At the same time, checks should be made of 

the store dry-bulb and wet-bulb temperatures 

to ascertain that they are within the limits 

prescribed by Hussmann.

d)  Complete start-up procedures should include 

checking through a defrost to make certain 

of its adequate frequency and length without 

substantially exceeding the actual needs. 

This should include checking the electrical 

or refrigerant circuits to make sure that 

defrosts are correctly programmed for all the 

refrigerators connected to each refrigeration 

system. 

e)  Recording instruments should be used to 

check performance.

Appendix C. - Field Recommendations - Refrigerated

Recommendations for field evaluating the 

performance of retail food refrigerators

1.0  The most consistent indicator of display 

refrigerator performance is temperature of the air 

entering the product zone (see Appendix A). In 

practical use, the precise determination of return 

air temperature is extremely difficult. Readings of 

return air temperatures will be variable and results 

will be inconsistent. The product temperature 

alone is not an indicator of refrigerator 

performance.

nOTe:  public Health will use the temperature of the product in 

determining if the refrigerator will be allowed to display 

potentially hazardous food. For the purpose of this 

evaluation, product temperature above the FDA Food 

Code 1993 temperature for potentially hazardous food 

will be the first indication that an evaluation should 

be performed. It is expected that all refrigerators will 

keep food at the FDA Food Code 1993 temperature for 

potentially hazardous food.

Summary of Contents for CRFD

Page 1: ...CRFD FLORAL Case p n IGFL CRFD CRFD 1 2 0508 INSTALLATION OPERATION GUIDE CHINO CRFD CRFD 1 2 FLORAL CASE Rev 0508 Installation Operation Manual...

Page 2: ...ipping damage before and during unloading This equipment has been carefully inspected at our factory and the carrier has assumed responsibility for safe arrival If damaged either apparent or concealed...

Page 3: ...2 62 1 4 C L 46 3 8 61 3 8 53 3 8 CRFD 1 2 Self Contained Plan View Scale 1 4 Drain 38 3 8 1 9 3 4 20 62 1 4 T 12 Lights 17 1 2 Booster Evap Pan CRFD Side View Scale 1 4 53 7 8 4 1 2 99 1 4 8 3 8 9 7...

Page 4: ...n these parameters to achieve near constant product temperatures Product temperature should be measured first thing in the morning after having been refrigerated overnight Defrost times should be as d...

Page 5: ...glass Sightglass Condensate Evaporator The condensate evaporator is a 5000 watt heater unit located on the lower back of the unit inside the condensate pan It is designed to evaporate water that comes...

Page 6: ...il User Information Stocking Improper temperature and lighting will cause serious product loss Discoloration dehydration and spoilage can be controlled with proper use of the equipment and handling of...

Page 7: ...inate this bacteria 1 Scrub thoroughly cleaning all surfaces with soap and hot water 2 Rinse with hot water but do not flood 3 Apply the sanitizing solution according to the manufacturer s directions...

Page 8: ...ase Model and Serial Number handy This information is on a plate located on the case itself Electrical Wiring Diagrams CRFD 2000W Evap 1 2 case 7 W0400003 Floral Display 220 VAC 50 Hz version T8 7 W04...

Page 9: ...ressor Heater Switch MagneTek 213 TC P MagneTek 213 TC P 240V 1 50Hz 20 2A Heating Element 2000W 240V High Limit Thermodisk Float Switch Condensate Evaporator G L1 N LIGHTS Toggle Switch 300W 220V 115...

Page 10: ...Switch High Limit Thermodisk Float Switch note case must be grounded Loads amp 240V 35 0 L1 black N L1 G J BOX 12 black 12 white 12 green blue 220V 1 50 60Hz Pressure Safety C ompress or 208 230V 2 H...

Page 11: ...R EVAPOWAY DM20WW 3D 2000W 240 VAC 125 01 0500 SAFETY SWITCH FLOAT SWITCH CONDENSING UNITS COPELAND F9AD B225 CFV 140 2 H P R 22 225 03 0111A POWER 208 230 VAC 1 50 60 HZ 4W M M START RUN CAPACITORS C...

Page 12: ...LL HBL 1372 125 01 0312 FISHER EVAPOWAY DM20WW 3D 2000W 240 VAC 125 01 0500 SAFETY SWITCH FLOAT SWITCH CONDENSING UNITS COPELAND F9AD B225 CFV 140 2 H P R 22 225 03 0111A POWER 208 230 VAC 1 50 60 HZ...

Page 13: ...HUBBELL HBL 1372 125 01 0312 SAFETY SWITCH FLOAT SWITCH FISHER EVAPOWAY DM20WW 3D 2000W 240 VAC 125 01 0500 SAFETY SWITCH FLOAT SWITCH CONDENSING UNITS COPELAND F9AD B225 CFV 140 2 H P R 22 225 03 01...

Page 14: ...OUNTING PLATE PART NUMBER 125 01 8515 WHITE 14 AWG BLACK 12 AWG BLACK 12 AWG BLACK 8 AWG BLACK 14 AWG WHITE 14 AWG RED 8 AWG BLACK 12 AWG RED 12 AWG RED 12 AWG RED 12 AWG RED 12 AWG BLACK 12 AWG BLK 1...

Page 15: ...LACK 12 AWG BLACK 8 AWG BLACK 14 AWG WHITE 14 AWG RED 8 AWG BLACK 12 AWG RED 12 AWG RED 12 AWG RED 12 AWG RED 12 AWG BLACK 12 AWG BLK 14 AWG WHITE 14 AWG T X 4 N 3 1 2 DEFROST TIMER PARAGON 8045 20 20...

Page 16: ...MOUNTING PLATE PART NUMBER 125 01 8515 WHITE 14 AWG BLACK 12 AWG BLACK 12 AWG BLACK 8 AWG BLACK 14 AWG WHITE 14 AWG RED 8 AWG BLACK 12 AWG RED 12 AWG RED 12 AWG RED 12 AWG RED 12 AWG BLACK 12 AWG BLK...

Page 17: ...25 02 1082 FAN MOTOR 3 GE 9W 115V 125 01 0615A M TERMINAL BLOCK 125 01 0295 POWER 208 230 VAC 1 50 60 HZ 4W M M EVAPORATOR FAN MOTOR FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082...

Page 18: ...M M TERMINAL BLOCK 125 01 0295 FISHER EVAPOWAY DM20WW 3D 2000W 240 VAC 125 01 0500 POWER 208 230 VAC 3 50 60 HZ M EVAPORATOR FAN MOTOR FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1...

Page 19: ...A M TERMINAL BLOCK 125 01 0295 POWER 115 VAC 1 60 HZ M M EVAPORATOR FAN MOTOR FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C23...

Page 20: ...15V 125 01 0615A M TERMINAL BLOCK 125 01 0295 POWER 115 VAC 1 60 HZ M M EVAPORATOR FAN MOTOR FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082 FIXTU...

Page 21: ...82 FAN MOTOR 3 GE 9W 115V 125 01 0615A M TERMINAL BLOCK 125 01 0295 POWER 208 230 VAC 1 50 60 HZ 4W M M EVAPORATOR FAN MOTOR FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082 FIXTURE...

Page 22: ...5 02 1082 FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082 FIXTURE LITHONIA C232 125 02 1082 FUSE 125 01 3282 15 AMP FUSE FUSE HOLDER 125 01 3283 FUSE 125 01 3282 15 AMP FUSE FUSE H...

Page 23: ...ING UNIT T STAT CONDENSING UNIT LIGHT SWITCH 125 01 0307 CANOPY LIGHTING 8 F32T8 48 LAMP 125 03 1073 4 LIGHT FIXTURE 125 02 1082 FAN MOTOR 3 GE 9W 115V 125 01 0615A M M TERMINAL BLOCK 125 01 0295 FISH...

Page 24: ...GHT SWITCH 125 01 0307 CANOPY LIGHTING 8 F32T8 48 LAMP 125 03 1073 4 LIGHT FIXTURE 125 02 1082 FAN MOTOR 3 GE 9W 115V 125 01 0615A M M TERMINAL BLOCK 125 01 0295 FISHER EVAPOWAY DM20WW 3D 2000W 240 VA...

Page 25: ...40VAC 125 01 0500 CONDENSATE EVAP PAN SAFETY SWITCH FLOAT SWITCH DT 140digi 20 240 125 01 0717 N RELAY RELEASE TIME T 1 2 X 4 F 3 EVAP PAN 2000W 8 3A 240VAC 125 01 0500 CONDENSATE EVAP PAN SAFETY SWIT...

Page 26: ...4 The installer should perform a complete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly...

Page 27: ...product 2 Is the product loaded beyond the Safe Load Line markers 3 Are the return air ducts blocked 4 Are the entering air ducts blocked 5 Is a dumped display causing turbulent air flow and mixing wi...

Page 28: ...temperature recovery Food store refrigerators are not food chillers nor can they reclaim quality lost through previous mishandling d Care must be taken when cross merchandising products to ensure that...

Page 29: ...____________________________ _______________ ___________________________________________________________________________________________________ _______________ _______________________________________...

Reviews: