P/N 0463857_C

REFRIGERATION DATA

Note: 

This data is based on store temperature and

humidity that does not exceed 75

°

F and 55% R.H. 

D5X-HE

Discharge Air °F

32

Evaporator °F

24

Unit Sizing °F

22

Btu/hr/ft — Unlit Shelves

D5X-HE

‡‡

Parallel

Conventional

U

NLIT

1280

1365

P

EG

*

1400

1485

* Hussmann Peg Shelves (Deli only).

‡‡ Add 10 Btu/hr/ft 

per shelf row

for LED fixtures.

Add 20 Btu/hr/ft 

per shelf row

for fluorescent lamps.

DEFROST DATA

Frequency Hrs

6

Defrost Water (lb/ft/day)

10.5

(± 15% 

based on case configuration and product

loading).

O

FFTIME

D5X-HE

Temp Term °F

48

Failsafe Minutes

35

E

LECTRIC OR

G

AS

Not Recommended

Standard Defrost Thermostat 

Close on rise: close 48°F  —  open 33°F 

CONVENTIONAL CONTROLS

Low Pressure Backup Control

CI/CO

**

D5X-HE

17°F / 7°F

Indoor Unit Only, Pressure Defrost

Termination**

48°F

**Use a Temperature Pressure Chart to determine

PSIG conversions.

Estimated Charge (lb)***

D5X-HE

4 ft

1.4

6 ft

1.9

8 ft

2.7

12 ft

3.9

***This is an average for all refrigerant types.

Actual refrigerant charge may vary by

approximately half a pound.

Impact  

Excel

D5X-HE

Dairy & Delicatessen

3 of 8

HUSSMANN CORPORATION • BRIDGETON, MO  63044-2483 U.S.A. • WWW.HUSSMANN.COM

31 

5

/

(804)

30 

1

/

4   

(768)

33 

1

/

(851)

30 

1

/

4

 

(768)

61

 

(1549)

42 

1

/

8

 

(1069)

46 

7

/

8

 

(1190)

FAN

L

D5X-HE

25 

1

/

4

 

(641)

3 In. 

(77 mm) 

Required 

Air Gap

81 

3

/

4

 

(2077)

1

/

(183)

27 

5

/

8

 

(702)

5

/

8

 

(92)

26 

1

/

(665)

Refrigeration 

Outlet

42

 

(1064)

Electrical 

Case to Case 

Connections

3

/

(120)

17 

1

/

(436)

7

/

8

 

(123)

Dimensions shown as in. and (mm).

Multi-deck, 5 Display Levels

NSF Certification

This merchandiser model is manufactured to meet ANSI/NSF
(National Sanitation Foundation) Standard #7 requirements for
construction, materials & cleanability.

Summary of Contents for D5X-HE

Page 1: ...Blade FB 0142780 7W Energy Efficient Fan Assembly 1 0477654 Fan Motor Evaporator MO 4410545 0142780 Fan Blade FB 0142780 Item Part Description Wiring Item THERMOSTATS B 0411744 Standard Non adjustabl...

Page 2: ...ternal legs and center legs NA 29 1 2 750 41 1 2 1054 41 1 2 1054 Distance between edges of center legs NA NA NA 43 7 8 1114 Distance between front legs and splashguard 2 3 4 70 2 3 4 70 2 3 4 70 2 3...

Page 3: ...F 7 F Indoor Unit Only Pressure Defrost Termination 48 F Use a Temperature Pressure Chart to determine PSIG conversions Estimated Charge lb D5X HE 4 ft 1 4 6 ft 1 9 8 ft 2 7 12 ft 3 9 This is an aver...

Page 4: ...ver Current Protection 120V 20 20 20 20 Maximum Over Current Protection 230V 15 15 15 15 Standard Lighting T 8 fluorescent 1 Row Canopy 0 26 0 51 0 51 0 77 30 59 59 85 Optional Lighting T 8 fluorescen...

Page 5: ...87 m3 m ARI Total Display Area 3 Sq Ft Ft 4 13 ft2 ft 1 26 m2 m Shelf Area 4 Sq Ft Ft 9 89 ft2 ft 3 02 m2 m 1 Computed using ARI 1200 standard methodology Refrigerated Volume ft3 m3 Unit of Length ft...

Page 6: ...R Optional Lighting 1 Row Rail B 4 ft 6 ft or 8 ft 12 ft 4 ft 6 ft or 8 ft 12 ft R Red Y Yellow G Green BL Blue B Black W White 120V POWER 120V NEUTRAL FIELD GROUND WARNING All components must have me...

Page 7: ...components must have mechanical ground and the merchandiser must be grounded CIRCLED NUMBERS PARTS LIST ITEM NUMBERS CASE GROUND Optional Shelf Harness and Light Circuits for Five Rows of Shelves 4 ft...

Page 8: ...R BL R BL R BL 7 7 7 7 7 7 7 R BL 6 B B W W BL R R BL R BL R BL R BL R BL R BL R BL 7 7 7 7 7 7 7 R BL 6 B B W W BL R R Red G Green BL Blue B Black W White 120V POWER 120V NEUTRAL FIELD GROUND WARNIN...

Reviews: