background image

3 of 8

P/N 0408922

HUSSMANN CORPORATION, Bridgeton, MO  63044-2483  U.S.A.

/

8

25

3

(645)

(Note:* Optional Accessory Items)

3

 

3

/

4 (95)

19

(483)

43

 

1

/

4

(1092)

19

(483)

5

 

3

/

8 (136)

27

 

5

/

8 (703)

29

 

1

/

4 (743)

30

 

5

/

8 (778)

34

 

5

/

8 (881)

38

 

7

/

8 (986)

46

 

1

/

2 (1182)

8

 

5

/

8

(219)

18

(406)

30

 

1

/

2

(775)

20

(508)

C2SLE

Multideck,  2  Display Levels, Low Back

Impact  

C2SLE

Delicatessen/Dairy

Precut & Packaged Produce

Dimensions are shown as in. & (mm).

REFRIGERATION DATA

Note:

This data is based on store temperature

and humidity that does not exceed 75

°

F and

55% R.H.   

C2SLE

Discharge Air (°F)

27

Evaporator (°F)

21

Unit Sizing (°F)

19

Btu/hr/ft*

C2SLE

Parallel

950

Conventional

1000

*For all refrigeration equipment other than

Hussmann, use conventional Btu values.

DEFROST DATA

C2SLE

Frequency (hr)

6

Defrost Water (lb/ft/day)

6

(± 15% 

based on case configuration and

product loading).

O

FFTIME

C2SLE

Temp Term (°F)

48

°

Failsafe (min)

30

Standard Defrost Thermostat

Close on rise: close 48

° 

—  open 33

° 

CONVENTIONAL CONTROLS

Low Pressure Backup Control

C2SLE

CI/CO (Temp °F)

**

17°/ 7°

Indoor Unit Only, Pressure Defrost
Termination (Temp °F)

**

48°  

**Use a Temperature Pressure Chart to
determine PSIG conversions.

PHYSICAL DATA

Merchandiser
Drip Pipe (in.)

1 1/2

Liquid Line (in.)

3/8

Suction Line (in.)

7/8

Estimated Charge (lb)***

C2SLE

4 ft 

1.3

6 ft 

1.8

8 ft 

2.3

12 ft 

3.3

***This is an average for all refrigerant
types. Actual refrigerant charge may vary by
approximately half a pound.

Length Added to Lineup by:
Each End/Partition (in.)

1 1/2

Note:

The bumpers are 4 in. wide. The center of the top bumper is 14 

1

/

8

in. 

from the floor and the center of the lower bumper is 6 

1

/

8

in. from 

the floor.

NSF Certification

These merchandisers are manufactured to meet ANSI/National
Sanitation Foundation (NSF

®

) Standard #7 requirements.

Summary of Contents for Impact C2SLE

Page 1: ...LIES AND THERMOSTATS A 6W Fan Assembly 1 0058698 Fan Motor Evaporator 115V 6W CW 0142780 Fan Blade embossing toward motor 8 in 25 CW B 0411744 Standard Non adjustable 2 disc type Defrost Thermostat C...

Page 2: ...kidrail and splashguard 7 178 7 178 7 178 7 178 Electrical Service B RH end of case to the center of LH knockout 40 1 4 1022 64 1 4 1632 88 3 8 2245 136 1 2 3467 Back O S of case to center of knockout...

Page 3: ...y 6 15 based on case configuration and product loading OFFTIME C2SLE Temp Term F 48 Failsafe min 30 Standard Defrost Thermostat Close on rise close 48 open 33 CONVENTIONALCONTROLS Low Pressure Backup...

Page 4: ...Anti sweat Heaters NA NA NA NA NA NA NA NA Min Circuit Ampacity With Standard Fans 0 70 1 20 1 20 1 70 Energy Efficient 0 46 0 72 0 72 0 98 Export 230V 50 hz 0 48 0 76 0 76 1 04 Max Over Current Prot...

Page 5: ...llow G Green BL Blue B Black W White WARNING All components must have mechanical ground and the merchandiser must be grounded CIRCLED NUMBERS PARTS LIST ITEM NUMBERS 1 2 3 Fans Optional Shelf Harness...

Page 6: ...BL BL 4 R 5 5 5 W 120V POWER 120V NEUTRAL WARNING All components must have mechanical ground and the merchandiser must be grounded Grayed components in 12 ft models only R Red Y Yellow G Green BL Blue...

Page 7: ...it must comply with the angle depth requirements listed below Maximum Shelf Shelf Angle Depth 0 12 in 15 14 in or less 30 16 in or less 45 16 in or less NOTE Shelves placed in the lower positions may...

Page 8: ...erchandiser when facing case To access the ballast 1 Remove screws at bottom edge of the canopy and rear of the top panel 3 Remove the one piece canopy top panel by moving panel forward slightly to cl...