background image

22 

1

/

2

 

(572) 

25

  5/8 (651)

28

 

3

/

4  

(730)

34

 

( 8 6 4 )  

13 

3/

(349) 

33

 

3

/

8  

(849)

44

 

5

/

8  

(1133)

FA N

11

  3

/8 

( 2 8 9 )  

46

  

(1168)

Refrig. 

Outlet

Elec.

FA

N

DA

O

C O I L

5/

(92)

7

 

3/

(308) 

33

 5

/8 

(854)

18 

1

/

2

 

(470) 

Impact  

IEDG1

Delicatessen

Dimensions shown as inches & (mm).

REFRIGERATION DATA

Note: 

This data is based on store

temperature and humidity that does not
exceed 75

°

F and 55% R.H.

IEDG1

Discharge Air (°F)

24

Evaporator (°F)

14

Unit Sizing (°F)

12

Btu/hr/ft

Parallel

390

Conventional

420

DEFROST DATA

IEDG1

Frequency (hr)

12

Defrost Water (lb/ft/day)

0.20

(± 15% 

based on case configuration and

product loading).

O

FFTIME

IEDG1

Temp Term (°F)

43

Failsafe (minutes)

90 

E

LECTRIC OR

G

AS

Not Recommended 

CONVENTIONAL CONTROLS

Low Pressure Backup Control

IEDG1

CI/CO* 

7°F / -3°F

Cut Out Pressure = Cut In, less 10 PSIG.

Indoor Unit Only, Pressure Defrost
Termination (Temp °F)*

Not Recommended

*Use a Temperature Pressure Chart to
determine PSIG conversions.

PHYSICAL DATA

Merchandiser

IEDG1

Drip Pipe (in.)

1 1/2

Liquid Line (in.)

3/8

Suction Line (in.)

5/8

Estimated Charge (lb)** 

8 ft 

1.5

12 ft 

2.0

**This is an average for all refrigerant
types. Actual refrigerant charge may vary
by approximately half a pound.

Length Added to Lineup by:
Each 

Plastic

End w/ 

Bumper 

(in.)

3 1/2

Each End/Partition (in.)

1 1/2

Flat Glass, 1 Display Level

3 of 6

P/N 0431338_A

HUSSMANN CORPORATION • BRIDGETON, MO  63044-2483 U.S.A. • WWW.HUSSMANN.COM