FAN
C
O
I
L
4
(102)
6
1
/
2
(165)
P1X
4
1
/
2
(114)
30
1
/
8
(765)
27
1
/
2
(699)
30
3
/
8
(770)
4
(102)
29
1
/
2
(749)
35
1
/
8
(891)
46
1
/
4
(1174)
16
5
/
8
(421)
53
1
/
8
(1349)
25
1
/
2
(648)
17
3
/
8
(441)
20
(509)
REFRIGERATION DATA
Note: This data is based on store tempera-
ture and humidity that does not exceed
75°F and 55% R.H.
P1X
P1XE
Discharge Air °F
31
31
Evaporator °F
21
24
Unit Sizing °F
19
22
Btu/hr/ft**
P1X
P1XE
Parallel
603
575
Conventional
638
610
**For all refrigeration equipment other than
Hussmann, use conventional BTU values.
DEFROST DATA
P1X
P1XE
Frequency (hr)
8
8
Defrost Water (lb/ft/day)
4
4
(±15% based on case configuration and
product loading.)
O
FFTIME
P1X
P1XE
Temp Term °F
43°F
43°F
Failsafe Minutes
35
35
E
LECTRIC OR
G
AS
Not Recommended
Standard Defrost Thermostat
Close on rise: close 43°F — open 33°F
CONVENTIONALCONTROLS
Low Pressure Backup Control
P1X
P1XE
CI/CO**
14/4°F 17/7°F
Indoor Unit Only, Pressure Defrost
Termination**
48°F
**Use a Temperature Pressure Chart to
determine PSIG conversions.
PHYSICAL DATA
Merchandiser Drip Pipe (in.)
1
1
/
2
Liquid Line (in.)
3
/
8
Suction Line (in.)
5
/
8
Estimated Charge (lbs)***
P1X
P1XE
8 ft
1.5
1.7
12 ft
2.0
2.3
***This is an average for all refrigerant
types actual refrigerant charge may vary by
approximately half a pound.
Length (in.) Added to Lineup by Each
End or Insulated Partition
1
1
/
2
Impact
P1X
Bulk Produce
Single Deck, High Back, 1 Display Level
Dimensions shown as inches and (mm).
NSF Certification
These merchandisers are manufactured to meet ANSI /National
Sanitation Foundation (NSF ®) Standard #7 requirements.
3 of 4
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
P/N 00457220