REFRIGERATION DATA
Note:
This data is based on store
temperature and humidity that does not
exceed 75
°
F and 55% R.H.
FF
IC
Discharge Air (°F)
–5
–12
Evaporator(°F)
–11
–19
Unit Sizing (°F)
–14
–22
Btu/hr/door/side*
FF
IC
Parallel
1180
1244
Conventional
1200
1270
*Optional LED lighting reduces the
refrigeration load by 100 Btu/hr/Door.
DEFROST DATA
FF
IC
Frequency (hr)
24
24
Defrost Water
(lb/Dr/side/day)
1.2
1.2
(± 15%
based on case configuration and
product loading).
E
LECTRIC
FF
IC
Temp Term (°F)
48
°
48
°
Failsafe (minutes)
45
45
G
AS
Duration
(minutes)
20
20
O
FFTIME
Not Recommended
CONVENTIONAL CONTROLS
Low Pressure Backup Control
FF
IC
CI/CO (Temp °F)
**
–18°/ –34° –26°/ –45°
Indoor Unit Only, Pressure Defrost
Termination (Temp °F)
**
Not Recommended
**Use a Temperature Pressure Chart to
determine PSIG conversions.
PHYSICAL DATA
Drip Pipe (in.)
1
1
/
4
Liquid Line (in.)
3/8
Suction Line (in.)
7/8
Estimated Charge per Side (lb)***
2Dr
1.8
3Dr
2.7
4Dr
3.6
5Dr
4.6
***This is an average for all refrigerant
types. Actual refrigerant charge may vary
by approximately half a pound.
Length Added to Lineup by each
Standard End (in.)
2
Optional End with Window (in.)
1
1
/
2
Optional Partition (in.)
1
1
/
2
Impact
RLNI
With
INNOVATOR Doors
Frozen Food & Ice Cream
3 of 6
P/N 0435492_G
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM
72
(1835)
67
(1724)
70
(1780)
63
(1603)
60
(1537)
4
(121)
9
(232)
11
(281)
82
3
/
8
(2091)
83
1
/
2
(2120)
Dimensions shown as in. & (mm).
NSF Certification:
These merchandisers are manufactured to meet
ANSI/National Sanitation Foundation (NSF
®
) Standard #7 requirements.