background image

5 of 6

P/N 0435492_G

Defrost Termination

Thermostat

Refrigeration

Thermostat

(Optional)

Pink

2

3

}

To
Condensing
Unit

A.S. Relay

Coil

BR

Evaporator Fans

1

Fan Relay

COM

N.O.

Rod Heater (Drain) 

9

Y

Y

N.C.

7

7

1

3

W

B

Relay Control

c

25

Fan Relay

B

5

6

B

B

COM

N.C.

6

A.S. Relay

A.S.

24

Door A.S. Heaters

Frame A.S. Heaters

21

22

2P

P

2P

P

12

11

10

120V P

OWER

16

13

OR

L

120V POWER

OR

Switch

N

EUTRAL

17

20

Evaporator Fan

Relay Coil

1

3

Rear Defrost Heater

R

R

C

8

R

R

Front Defrost Heater

R

5

4

B

B

7

R

N.C.

7

8

8

Defrost Limit

208V

208V

Terminal Blocks in Raceway

Low Temperature with

Electric Defrost

20

21

22

26

17

1

2

3

4

5

6

7

8

10

11

14

13

16

LIGHTS

(120V)

DEFROST HEATERS

(208V)

CIRCLED NUMBERS = PARTS LIST ITEM NUMBERS

THESE ARE MARKER COLORS (WIRE MAY VARY.)

CAUTION:

  When multiplexing

merchandisers equipped with defrost
heaters, if branch circuit overcurrent
protection is larger than the
individual merchandiser’s defrost
circuit load, then additional
supplemental overcurrent protection
may be required per NEC Articles
210 and 240.

R = Red    P = Purple   2P = Purple (2 Bands)   DB = Dark Blue   B = Black

 BR =Brown  Y =Yellow   OR = Orange   W = White   

24

25

12

FANS & A.S.

 (120V)

LIGHTS

(Neutral)

FANS & A.S. (Neutral)

Permanent Internal

 Jumpers

R

P

W

BR

OR

R

R

R

B

B

R

R

B

P

2P

B

B

OR

B

2P

Y

14

26

C.O.R.

1

2

3

4

6

O.O.R.

Removable External

Jumpers

DB

C.O.R.

2

Defrost Termination

Thermostat

FIELD WIRED

DB

N

EUTRAL

Dark Blue

Refer to 

Innovator Reach-In

Glass Door, Installation and
Service

 manual, P/N 0425683,

for 

Innovator

 door and frame

replacement parts.

Electric Defrost Sequence - Low Temperature

1.

Power from the defrost contactor energizes Defrost Heaters and 208V Evaporator Fan Relay Coil (7).  Relay Contacts open the fan
circuit and energizes the Drain Pan Heater.

2.

If the Defrost Heater raises internal air temperature above 90°F, the Defrost Limit Thermostat (4) will open.

3.

Temperature rise of the evaporator closes the Relay Control Thermostat (5) at about 35°F, energizing 120V A.S. Relay Coil (6). This
relay’s contacts open the Frame and Door Heater Circuits.

4.

When Defrost Termination Thermostat ends defrost period, the defrost contactor opens the Defrost Heater and Evaporator Fan Relay
Coil Circuits.  The Drain Pan Heater goes off and fans are on.

5.

Temperature fall of the evaporator opens the Relay Control Thermostat (5) at about 20°F, de-energizing 120V A.S. Relay Coil (6).
A.S. Relay Contacts close the Frame and Door Heater Circuits. 

Fan and Heater Circuits — Electric Defrost (standard)

Low Temperature

Wiring Diagram is per side — two circuits required per case.

Wiring Diagram is per side — two circuits required per case.

Reviews: