Proto-Aire EZ I/O Manual
P/N
3090249_E
26
Sample
Proto-Aire EZ
Checklist
Store:
QT
Market
Location: Anytown, USA
Date:
7
/
30
/20
18
Time:
Unit
A
Model Number
Serial Number
Factory Order Number
Manufacture Date
0
7
/
30
/
20
20
Defrost
Circuit NO.
1
2
3
4
5 / 6
Type
Off
Off
Off
Off
Off /
No./Day
2
3
3
2
1 /
Length
40m
45m
45m
45m
60m /
Superheat
2
6
°
F
Suction Set Point
52 psig
Suction Pressure
52.0 psig / 17°F Saturated
Suction Temperature
17
°
F
Split/Satellite Superheat
Suction Set Point
Suction Pressure
Suction Temperature
Oil
POE
Oil Separator
Between Glasses
Pressure Differential
Condenser
Head Pressure
214.9 psig
Water Temperature In
OK
Water Temperature Out
OK
Refrigerant
4
48
a
Receiver Level
Liquid Sight Glass
Foamy
Compressor No.
1
2
3
Model No.
ZBD57KCE ZB57KCE ZB57KCE
Discharge Temperature
173
°F
166
°F
166
°F
Amp Draw
10.2
10.7
10.8
Shell Temp at Oil Connect
hot
hot
warm
Float or Oil Connect
¾
Oil Control Magnet Cond.
Controller
Alarms
Time & Date Displayed
Notes:
L.L. Filter changed
All
TXV
valves adjusted.
Raised suction S.P. from 48 psig to 52 psig. All
cases are
cleaned.
¾
¾
Use this form as a guide for your store’s checklist on the following page.