Rev. 9610(9911)
5
Plumbing
ACCESS PANELS
The drain line is accessable through a panel on the interior
back wall if the case on the left hand side..
DRAIN AND P-TRAP
The drain line is located on the left hand side of the case.
There are two drain lines for back to back (double sided)
cases.
WASTE OUTLET AND P-TRAP
The waste outlet is located off the center of the case on
one side allowing drip piping to be run lengthwise under
the fixture.
A 1-1/2" P-trap and threaded adapter are supplied with
each fixture. The P-trap must be installed to prevent air
leakage and insect entrance into the fixture.
NOTE: PVC-DWV solvent cement is recommended.
Follow the manufacturer’s instructions.
INSTALLING CONDENSATE DRAIN
Poorly or improperly installed condensate drains can se-
riously interfere with the operation of this refrigerator,
and result in costly maintenance and product losses. Please
follow the recommendations listed below when installing
condensate drains to insure a proper installation:
1.
Never use pipe for condensate drains smaller than
the nominal diameter of the pipe or P-trap supplied
with the case.
2.
When connecting condensate drains, the P-trap
must be used as part of the condensate drain to
prevent air leakage or insect entrance. Store
plumbing system floor drains should be at least 14"
off the center of the case to allow use of the P-trap
pipe section. Never use two water seals in series in
any one line. Double P-traps in series will cause a
lock and prevent draining.
3.
Always provide as much down hill slope (“fall”) as
possible; 1/8" per foot is the preferred minimum.
PVC pipe, when used, must be supported to maintain
the 1/8" pitch and to prevent warping.
4.
Avoid long runs of condensate drains. Long runs
make it impossible to provide the “fall” necessary for
good drainage.
5.
Provide a suitable air break between the flood rim
of the floor drain and outlet of condensate drain. 1"
is ideal.
6.
Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should
be insulated with a nonabsorbent insulation
material such as Armstrong’s Armaflex.
b. Where condensate drains are located in dead air
spaces (between refrigerators or between a
refrigerator and a wall), provide means to
prevent freezing. The water seal should be
insulated to prevent condensation.
DRAIN ACCESS
LEFT SIDE
DRAIN ACCESS
LEFT SIDE
WARNING: DO NOT LET ANY WEIGHT BEAR
D OW N O N T H E C O I L A S S E M B LY. U S E 5
GALLON BUCKETS OR SIMILAR UNDER THE
CANOPY TO HOLD THE WEIGHT WHILE THE
BEAM IS BEING ATTACHED. THE FORK HOLES
ON THE BEAM SHOULD FACE TOWARD THE
OUTSIDE EDGE OF THE CANOPY.
5. Carefully raise and position Canopy on Center Wall
"C" channels. Fasten with screws provided - two on
each side of the C channel. "C" channels are located
every two feet along the length of the case.
6. Screw first panel of both End Panels to the Canopy to
stabilize the case. Shim to level
After cases have been leveled and joined, and refrigera-
tion, electrical, and wasted piping work completed, install
the splashguards. Fasten along the top edge, or center, with
#10 X 3/3" sheet metal screws.
D
O
N
OT
S
EAL
J
OINT
T
RIM
T
O
F
LOOR
!
Summary of Contents for RID
Page 14: ...IGUP RID 9610 9911 14 ...