background image

Notes:

The SELECT button is used to scroll through the following menus:

StUP

–  Setup 

CLoC

–  Clock 

dEFr

–  Defrost

tEM

–  Temperature

uALu

–  Valve 

diSP

–  Display Default

User must enter valid password to edit parameter settings.

To edit any menu item, press either the UP or DOWN button to

enter the selected menu.

Use the SELECT button to modify and save the parameter once the

UP or DOWN button is pressed.

The display cycles between menu item and edited menu value once

the edited value is entered using the SELECT button, .

The display returns to showing the product simulator temperature

if no button is pressed for 12 seconds once the menu is displayed. User

must scroll through the menus using the SELECT button to return to

the SETUP menu.

Holding a button down has the same effect as pressing once.

PASSWORD

Entering the password is done in the SETUP menu. At the top of the

SETUP menu, press the UP button. The display will begin to cycle

between PASS and 0.

While 0 is being displayed, press the SELECT button to allow editing

of the value. With the Safe-NET display module flashing 0, use the UP

/DOWN buttons to increment or decrement the value until it reaches

595.  595 is the password value.

Once 595 is displayed, press the SELECT button. The display will

revert to cycling between PASS and 595. This enables editing of

parameters. 

The user may now navigate the menu system and edit parameters as

necessary. 

Note:

The password protected access remains active for 5 minutes. Each time a
new parameter is entered by pressing the ENTER key on the Hand-Held
device or the SELECT button on the Safe-NET display module, the
5 minute timer is restarted. After 5 minutes with no parameter entries, 
the password value reverts to 0 and the password entry process must be
performed to regain access to critical parameters. The SETUP menu can
be navigated without a valid password in a “view only” mode.

MODIFYING SET POINTS

With the password active and the display reading product temperature,

use the SELECT button to scroll through the menus. Once the display

reaches the 

StuP

menu, use the UP button until the display shows the

parameter to be modified:

To change the product low alarm set point, press the UP button

until the display cycles between 

PrLo

and the current product low

alarm set point.

To change the product high alarm set point, press the UP button

until the display cycles between 

PrHi

and the current product high

alarm set point.

To change the product alarm delay, press the UP button until 

display cycles between 

P-dL

and the current product alarm delay.

Once the desired menu item is displayed, press SELECT button. The

display cycles between the corresponding menu item and the VALUE.

Press the UP button to increment the value or the DOWN button to

decrement the value. 

When the entered value begins flashing, press the SELECT button to

store the new value. The display cycles between the new value and the

menu item. Within 12 seconds after button activation, the display

starts showing the product temperature.

ALARMS

A red LED on the board turns on during alarm. The display will show

a four-character word for about 3 seconds alternating with a blank 

display for 9 seconds. Following are details of alarms applicable to 

self-contained cases.

Alarm with Sensor Number – “SEnS”

This alarm is generated when the control is initialized, and indicates

that the number of sensors entered in the control is different from the

number of sensors connected to the control. This Alarm can be cleared

only by changing the reading for number of sensors to 0 and resetting

the display module which then updates the reading to the number of

sensors connected. This is caused by the control not being set up 

correctly or by a sensor having failed.

Alarm with Sensor reading – “noSn”

This alarm is generated when the display module is unable to read the

sensors for five consecutive seconds. This alarm clears automatically

when the control is able to read the sensors. This may be caused by a

sensor being disconnected or shorted. This alarm clears automatically

when the control is able to read the sensors.

Discharge Air High Alarm – “dSHi”

This alarm is generated when the average discharge air temperature in

the case, over the programmed alarm delay time, is higher than the

High Alarm value stored in the control. This alarm will clear if the

average discharge air temperature goes below the High alarm value.

T

HIS ALARM IS AVAILABLE ONLY IF DISCHARGE SENSORS ARE INSTALLED

.

Discharge Air Low Alarm – “dSLo”

This alarm is generated when the average discharge air temperature in

the case, over the programmed alarm delay time, is lower than the Low

Alarm value stored in the control. This alarm will reset if the average

discharge air temperature goes higher than Low alarm value. 

T

HIS ALARM IS AVAILABLE ONLY IF DISCHARGE SENSORS ARE INSTALLED

.

Note:  

Programmable alarm delay (AdLy) is described in a later 

section.

Communication Alarm – “CoM”

If there are no network communication attempts for a period of more

than 30 minutes, the display module sets a communication alarm and

shows it on the display. When the display module itself is controlling

rather than (dSPn) a network, the Display Number in setup must be set

to “nonE”to prevent alarm generation.

Product High Temperature Alarm – “PrHi”

This alarm will be generated if the product simulator average is above

high alarm set-point for product alarm delay time 

T

HE

P

R

H

I AND

P

R

L

O ALARMS ARE AVAILABLE ONLY IF PRODUCT SENSORS ARE

INSTALLED

.

Product Low Temperature Alarm – “PrLo”

This alarm will be generated if the product simulator average is below

low alarm set-point for product alarm delay time.

Door Open Alarm

This alarm will be generated only if the input of the display is con-

nected to a door switch and the input configuration on the display

board is set to “door”. It is generated when the door is kept open for

more than 2 minutes and will be cleared when the door is closed.

The display alternates two words “cLoS”and “door”until the door is

closed.

Door Open

If the doors are left open for more than 5 minutes even after the alarm,

the fans are turned back on.

MENU NAVIGATION OVERVIEW

The presentation of the Safe-NET Menu system and associated button

and key operation vary somewhat according to the currently displayed

menu item and/or action to be performed. Individual menu items, 

definition of purpose, associated action and keypad/button behavior 

is described in detail in the following sections.

Some actions and behaviors of the Safe-NET Menu system are 

consistent throughout. These should be taken into account to avoid

confusion when navigating the Safe-NET Menu system.

TIME OUTS

Password

Once the valid ‘595’PASSWORD has been entered, it will remain active

for 5 minutes. A 5 minute timer is restarted each time a new value is

confirmed with the SELECT button on the Safe-NET Display module.

Re-setting the Safe-NET Display module clears the PASSWORD entry

and sets the 5-minute timer to 0. Therefore, if a setting is modified

that requires the Safe-NET Display module to be reset and subsequent

values require modification, the PASSWORD must be re-entered.

Inactivity

Anytime the display is moved from the default display whether a PASS-

WORD has been entered or values and settings are simply being viewed

and not modified, the display will revert to the default display after 10

seconds. This occurs if no key is pressed on the Hand-Held device or

button on the Safe-NET Display module. If a valid PASSWORD has

been entered, and the display reverts to the default display due to key-

pad and/or button activity, the PASSWORD will remain active for the

remainder of the aforementioned 5-minute timeout period. To resume

modifying values, re-enter the menu of interest while the PASSWORD

is active and continue modifying values. 

A modified value will revert to its original value if the value has been

modified but the SELECT button has not been pressed before 

simultaneously pressing the UP and DOWN buttons on the Safe-NET

Display module.

BUTTON ACTION

This photo identifies the buttons and the corresponding action on the

Safe-NET Display Module.

Safe-NET™ Self-contained Operating Instruction

Page 

3 of 8 — P/N 0485005_B

www.hussmann.com/cstore/c_techinfo.htm

© 2007 Hussmann Corporation • Bridgeton, Missouri  63044-2483 U.S.A.

20 June 2007

SELECT Button

UP Button

Safe-NET™ Display Module Button Action

DOWN Button

Summary of Contents for Safe-NET

Page 1: ... need for separate wiring Sensors in each case are harnessed together to a single wire leading to the display module Sensors are designed for rugged durability Should a sensor fail it can be replaced Optional Wireless Hand held Controller and or PC Control The wireless controller communicates with the display unit through an infrared sensor This allows setups and queries which can also be performe...

Page 2: ...ay module is lighted Every 12 seconds A Er is displayed for 3 seconds for the remaining time the product simulator temperature is displayed The beeper on alarm board beeps every 30 seconds The A Er audible alarm is active only when external power is applied Precedence of Alarms Severity of the alarm determines the beeper action The following table shows the priority of the alarms An alarm with hig...

Page 3: ...read the sensors DischargeAir HighAlarm dSHi This alarm is generated when the average discharge air temperature in the case over the programmed alarm delay time is higher than the HighAlarm value stored in the control This alarm will clear if the average discharge air temperature goes below the High alarm value THIS ALARM IS AVAILABLE ONLY IF DISCHARGE SENSORS ARE INSTALLED DischargeAir LowAlarm d...

Page 4: ...rdingly in the detailed parameter descriptions PASSWORD PROTECTION Parameters that are critical to proper equipment performance cannot be modified until a numeric password is entered into the Safe NET display module This prevents accidental or malicious changes in the Safe NET system from occurring Entering the password is done in the SETUP menu At the top of the SETUP menu press the UP button on ...

Page 5: ...g F the ON OFF control method will attempt to maintain the 10º by cycling the control device ON at temperatures above 10º and OFF at 0º This temperature control is superceded by a fixed minimum ON time of 3 minutes Hence lower DIFF settings will result in tighter temperature control but more frequent control device compressor valve cycling Conversely higher DIFF settings will reduce control device...

Page 6: ...at a valid PASSWORD be entered first DTYP The Safe NET system is capable of controlling defrost activity and scheduling The Safe NET system is capable of controlling six types of defrost OffC DET Mod ELE2 GAS and ELE1 1 OffC Off Cycle During off cycle defrost refrigeration to the fixture is stopped by either cycling off the compressor if so equipped shutting off the liquid line solenoid valve shut...

Page 7: ...ed as represented to the right Missing or non connected sensors will not appear in the designated sequence Average temperatures are available to view so long as the associated sensing devices are attached DSAV DischargeAirAverage RTAV ReturnAirAverage PDAV ProductAverage T LO LowestTermination Sensor Reading ILET Evaporator Inlet OLET Evaporator Outlet TSNL LeftTermination Sensor TSNC CenterTermin...

Page 8: ...e desired setting is displayed press the SELECT button on the Safe NET display module to store the new value to NV memory The display will revert to cycling between DISP and the new value Note One or more sensors of the type selected must be installed to support the selection Alarm Module OPTIONAL The alarm module is an additional feature to Safe NET The alarm module supplies power to the display ...

Reviews: