background image

Page 8 

Because of the CFC atmospheric considerations 
being  taken today, we ask that leak testing be 
done with refrigerant 22 mixed with nitrogen.  If 
the condensing unit nameplate designates a re-
frigerant  other than R-22, remove all R-22 from 
the immediate area to avoid confusion after leak 
testing and evacuating the unit.  Recharge the 
unit with proper refrigerant. 
 
LEAK TESTING –  
 
 

The test gas cylinder must be equipped 

with a pressure gauge and regulator so that sys-
tem test pressures do not exceed maximum allow-
able limits.  Do not ever use anything other than a 
R-22/Nitrogen mixture for leak testing. 
 
 

Attach a refrigerant test gas cylinder to 

your service manifold and connect the manifold 
to the charging port on the liquid line valve.  
Charge an R-22/Nitrogen mixture into the sys-
tem, raising the pressure to the unit’s nameplate 
for the low side and high side pressures.  Using an 
electronic detector, carefully check the entire sys-
tem for leaks.  Take special care to inspect all 
brazed and flare connections. 
 
EVACUATION –  
 
 

After the system is proven leak tight, thor-

oughly evacuated the system according to the fol-
lowing procedure: 
 
1.  Discharge the refrigerant-nitrogen mixture, 

allowing it to blow from the system as rapidly 
as possible, into an empty cylinder.  Be sure 
that all service valves and solenoid valves are 
open to allow all of the mixture to be dis-
charged. 

 
 
 
 

2.  Connect a deep-drain vacuum pump to 

both the high and low side of the sys-
tem.  Pull a vacuum on the system to at 
least 1500 microns. 

 
3.  Break the vacuum by adding refriger-

ant into the system until the pressure is 
above 0 PSIG.  Always charge the re-
frigerant line into the system through a 
new drier in the charging manifold line.  
A 16 cubic inch drier is sufficient for 
this purpose. 

 
4.  Repeat steps 2 and 3 two more times, 

the third time evacuating the system to 
500 microns. 

 
OPERATING DATA –  
 
 

The following is typical data for 

USL models based on lab tests, and may 
vary under field operating conditions. 
 

Ambient Temperature   

75ºF 

Head 

Pressure 

  225 

psi 

Suction 

Pressure 

  3-5 

psi 

Discharge 

Air 

  -25ºF 

Return 

Air 

  -10ºF 

 

COMPRESSOR –  
 
 

The compressor is mounted on 

springs and banded for shipping purposes 
and this band needs to be cut upon installa-
tion.  DO NOT LOOSEN THE COM-
PRESSOR MOUNTING BOLTS AS 
THESE ARE FACTORY PRE-SET FOR 
PROPER RIDING ON THE SPRINGS. 
 
RECEIVER –  
 
 

The receiver should not be confused 

for a filter-drier or muffler.  The receiver is  
 

 

 

Summary of Contents for USL-2

Page 1: ...URE Solid Door Reach In for Ice Cream and Frozen Foods P N OII USL January 2006 First Call for help US and Canada 1 800 922 1919 Soporte T cnico y Asistencia M xico 01 800 522 1900 For a Service Netwo...

Page 2: ...apacities 4 General Upkeep Care and Cleaning Routine Maintenance 4 Power Switches Temperature Control 5 Thermometer Electrical Enclosure 5 Defrost Time Clock 6 Defrost Heater Thermostat and Replacemen...

Page 3: ...xi mum operating efficiency INSTALLATION and START UP SKID The skid should be left on the cabinet until it is near the final location The skid pro vides protection for both the case and floor The skid...

Page 4: ...for durability and ease of cleaning Care should be taken when loading the shelves with product Product on the highest level of shelves should not touch the evapora tor drain pan This pan gets warm du...

Page 5: ...ps Size Wt USL 2 15 0 20 amp 875 BTU CAPACITIES Rating Temps F BTU HR Evap Cond Amb USL 2 2280 20 110 90 During June 95 R404A refrigerant was phased into use on the USL 2 The refriger ant charge is 46...

Page 6: ...obably need resetting to reflect the proper case temperature Using a separate thermometer located on a shelf in the case compare this temperature to that on the case thermometer If the case thermomete...

Page 7: ...lowest usage Defrost is time initiated and tempera ture terminated If the thermostat should fail the timer is equipped with a failsafe set at 40 minutes that will allow defrost to terminate on time DE...

Page 8: ...rature Adjust the expansion valve as follows 1 Attach two sensing probes to the evapora tor one under the clamp holding the ex pansion valve sensing bulb and the other securely taped to one of the ret...

Page 9: ...g to the fol lowing procedure 1 Discharge the refrigerant nitrogen mixture allowing it to blow from the system as rapidly as possible into an empty cylinder Be sure that all service valves and solenoi...

Page 10: ...pres sor will start properly On start up the valve will hold the suction pressure at the desired setting until the suction pressure has dropped below the setting then the valve will open If it becomes...

Page 11: ...e air flow restriction 3 Defective condenser fan mo tor 3 Replace 4 Air or non condensable gas ses in system 4 Leak check change drier evacuate and recharge Warm storage temperatures 1 Temperature con...

Page 12: ...temperature con trol 4 Replace 5 Power disconnected 5 Check service cord or wir ing connections Compressor will not start cuts out on overload 1 Low voltage 1 Contact electrician 2 Defective compress...

Page 13: ...nd R404 KAAB 007E CAA Condenser Fan Motor EMS ESPL25EM1 Evaporator Fan Motor Morrill SPB5EM1 Light Ballast 8G3738W Incandescent Lamp GE 40A15 WARRANTY AND PARTS INFORMATION Please read carefully to as...

Page 14: ...s will not be shipped from the Hussmann factory They may be obtained from your nearest Copeland Wholesaler Your wholesaler will replace free of charge any compressor found to be defective within twelv...

Page 15: ......

Reviews: