background image

VGM, VGD-0505

8

Refrigeration

THERMOSTATIC EXPANSION VALVE LOCATION

This device is located on the same side as the refrigera-
tion stub.  An ALCO expansion valve model is furnished
as standard equipment, unless otherwise specified by
customer.

EXPANSION VALVE ADJUSTMENT

There is one (1) valve on the right side of each coil.

M E A S U R I N G   T H E   O P E R A T I N G   S U P E R H E A T

1.

Determine the suction pressure with an accurate
pressure gauge at the evaporator outlet.

2.

From a refrigerant pressure temperature chart, de-
termine the saturation temperature at the observed
suction pressure.

3.

Measure the temperature of the suction gas at the
thermostatic remote bulb location.

4.

Subtract the saturation temperature obtained in step
No. 2 from the temperature measured in step No. 3.

5.

The difference is superheat.

6.

Set the superheat for 5

°

F - 7

°

F.

T - S T A T   L O C A T I O N

T-Stats are located within the electrical raceway. Refer to
diagram below.

CASE FRONT

DRAIN

MECHANICAL

STUB UP AREA

19" X 19"

CASE FRONT

T-STAT AND BALLAST LOCATIONS

WATER,
ELEC. &

REFRIG.

MECHANICAL

STUB UP AREA

19" X 19"

DRAIN

CL

B

T

B

SELF CONTAINED CASES

The only difference between a remote case and a self-
contained case is the addition of a condensing unit.

SELF CONTAINED START-UP

Self contained cases are totally ready to run once power
is supplied. All controls are set and units charged with
refrigerant.

DEFROST SET-UP

Defrost times vary according to case model - refer to
Case specification section in the back of the book for
proper duration and frequency. Self contained cases have
individual defrost time clocks. When power has been
applied, set the time clock to the proper duration and
frequency.
The time clock is located behind the front panel under
the case. Turn the clock dial counterclockwise until the
pointer is directed to the current time of day.

R E F R I G E R A N T   T Y P E

The standard refrigerant will be R-22 unless otherwise
specified on the customer order. Check the serial plate
on the case for information.

REFRIGERATION LINES

  LIQUID

SUCTION

3/8"  O.D.

 5/8" O.D.

NOTE: The standard coil is piped at 5/8" (suction); however, the

store tie-in may vary depending on the number of coils
and the draw the case has. Depending on the case setup,
the connecting point in the store may be

5

/

8

", 

7

/

8

", or 1

1

/

8

". Refer to the particular case you are

hooking up.

Refrigerant lines should be sized as shown on the
refrigeration legend furnished by the store.
Install 

P-traps

 (oil traps) at the base of all suction line

ver tical risers.

Pressure drop

 can rob the system of capacity. To keep the

pressure drop to a minimum, keep refrigerant line run as
short as possible, using the minimum number of elbows.
Where elbows are required, use long radius elbows only.

CONTROL SETTINGS

See the “Case Specs” section of this guidebook for the
appropriate settings for your merchandiser. Maintain
these parameters to achieve near constant product
temperatures. Product temperature should be measured
first thing in the morning, after having been refrigerated
overnight. For all multiplexing, defrost should be time
terminated.  Defrost times should as directed in the
Case Specifications section of this guide. The number of
defrosts per day should never change. The duration of
the defrost cycle may be adjusted to meet conditions
present at your location.

ACCESS  TO TX VALVES & DRAIN LINES

MECHANICAL

 - Remove product from end of case.

Remove product racks. Remove refrigeration and drain
access panels (labeled). TX valve (mechanical only) and
drain are located under each access panel at end of the
case.

ELECTRONIC

  - The Electronic Expansion valve master

and slave cylinder(s) are located within the electrical
access panel(s).

ELECTRONIC EXPANSION VALVE

 (OPTIONAL)

A wide variety of electronic expansion valves and case
controllers can be utilized.  Please refer to EEV and
controller Hussmanns information sheet.  Sensors for
electronic expansion valves will be installed on the coil
inlet, coil outlet, and in the discharge air. (Some super-
markets require a 4th sensor in the return air). Case
controllers will be located in the electrical raceway or
under the case

Summary of Contents for VGD

Page 1: ...VGM VGD Vertical Glass Service Deli Meat Fish Case P N VGM VGD 0505 Chino VGM VGD Vertical Glass Service Deli Meat Fish Case REV 0505 I n s t a l l a t i o n Operation M a n u a l INSTALLATION OPERAT...

Page 2: ...f Hussmann Chino notify Hussmann Chino If such a shortage involves the carrier notify the carrier immediately and request an inspection Hussmann Chino will acknowledge shortages within ten days from r...

Page 3: ...perature swings causing product dehydration and excessive energy consumption Defrost cycles should be set according to the Case Specifications in this book Clean humidity system a minimum of every 90...

Page 4: ...s full extension and lower Installation These steps should release any settled lubricant within the cylinders and prevent any stress on the front glass SETTING AND JOINING The sectional construction o...

Page 5: ...re by bolting the rear mullions tegether Do not use bolts to pull cases together 9 Apply bead of silicone to top of bulkheads and slip on stainless steel bulkhead cap Also apply silicone to seam betwe...

Page 6: ...trap supplied with the case 2 When connecting condensate drains the P trap must be used as part of the condensate drain to prevent air leakage or insect entrance Store plumbing system floor drains sh...

Page 7: ...oduct quality with the installation of the proper controlling devices These should be set according to the Hussmann s specifications and a prop erly maintained humidity system Incorrect settings and f...

Page 8: ...te on the case for information REFRIGERATION LINES LIQUID SUCTION 3 8 O D 5 8 O D NOTE The standard coil is piped at 5 8 suction however the store tie in may vary depending on the number of coils and...

Page 9: ...each night with a clean damp cloth or butcher paper never use plastic as it does not allow appearance and significantly shortening product shelf life 10 Cold coils remove heat and moisture from the ca...

Page 10: ...clean the non glare glass The damage to the glass from improper cautic solutions is irreparable In addition to cleaning the glass with the recommended product there are precautions that should be take...

Page 11: ...trol is working properly and that no outside doors or windows are open allowing moisture to enter store FOR PROMPT SERVICE When Contacting the Factory regarding problems Be sure to have the Case MODEL...

Page 12: ...ction gently tap loose or remove panel wedge the entire length of the panel Maintenance cont FOR PROMPT SERVICE When Contacting the Factory regarding problems Be sure to have the Case MODEL and SERIAL...

Page 13: ...s Disconnect Electrical Power at the Main Disconnect when servicing or replacing any electrical component This includes but not limited to Fans Heaters Thermostats and Lights ALWAYS DISCONNECT ELECTRI...

Page 14: ...AIR T STAT FAN SIZE FREQ AIR AIR HUNIDITY LENGTH REQ D EVAP PROD DISC VELOC CUT IN NUMBER FAN E E FANS RECEP SWEEP SWEEP SYSTEM APP FT TMP TMP TMP FPM SETTINGS EVAP COIL OF MOTORS QTY DURATION STANDA...

Page 15: ...F32T8 48 125 03 0241 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F32T8 48 12...

Page 16: ...FANS 1 COMAIR 125 01 2011 M F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28...

Page 17: ...NS 1 COMAIR 125 01 2011 M F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F28T5...

Page 18: ...03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F28T5 48 125 03 1132 F28T5 48 125 03 1132 F3...

Page 19: ...0311 CIRCUIT 1 W G BK DUPEX OUTLET SINGLE OUTLET W G BK AIR SWEEP FANS 3 COMAIR 00001212 M M M F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241 F32T8 48 125 03 0241...

Page 20: ...W G BK DUPEX OUTLET SINGLE OUTLET W G BK AIR SWEEP FANS 3 COMAIR 00001212 M M TOP FRONT LIGHTS OPTIONAL LIGHTS TERMINAL BLOCK 125 01 0295 SHELF LIGHT NOSE LIGHT LEDGE LIGHT F21T5 36 125 03 1129 F21T5...

Page 21: ...complete start up evaluation prior to the loading of food into the refrig erator which includes such items as a Initial temperature performance Coils should be properly fed with a refrigerant accordi...

Page 22: ...or blade inoperative 14 Is the defrost time excessive 15 Is the defrost termination thermostat if used set too high 16 Are the refrigerant controls incorrectly adjusted 17 Is the air entering the cond...

Page 23: ...this warranty shall be limited to a period not to exceed five years from date of factory shipment On Hussmann refrigeration systems an additional 4 year extended warranty for the motor compressor ass...

Page 24: ...lar unit They can be found on a small metal plate on the unit Please note them below for future reference M O D E L SERIAL NUMBER Chino Additional copies of this publication may be obtained by contact...

Reviews: