background image

- 3 - 

5  Main Technical Performance Indicators 

5.1  The main technical performance indicators are shown in Table 3. 

Table 3 Main technical performance indicators 

Shell frame level rated current 

Inm (A) 

63 

100 

250 

Product model 

H8M- 

63S 

H8M- 

100C  H8M-100S 

H8M- 

100H 

H8M- 

100U 

H8HM- 

250C 

H8M- 

250S 

H8M- 

250H 

H8M- 

250U 

Rated current In (A) 

10,16,20 

25,32,40 

50,63 

16,25,32,40,50,63,80,100 

100,125,150,160,175,200,225,250 

Number of poles 

Rated insulation voltage Ui (V)  AC 600 

AC 800 

AC 800 

Rated impulse withstand 

voltage Uimp (kV) 

Flashover distance (mm) 

≤50(0)*

 

≤50 (0) *

 

≤50 (0) *

 

Rated 

ultimate/service 

short-circuit 

breaking 

capacity Ics (kA) 

690 V 

5/3 

10/5  10/5 

5/5 

10/5 

10/5 

400 V 

35/35 

35/35 

55/55 

85/85  125/ 

125 

35/35 

55/55 

85/85  125/ 

125 

Operation 

performance 

(times) 

Energizing 

8,000 

8,000 

8,000 

De-energizing  20,000 

20,000 

20,000 

Outline dimensions 

(mm) 

 

75 

90  120 90  120 

90 

90 

105  140  105  140  105  105 

130 

155 

216 

165 

240 

68 

68 

68 

Installation dimensions 

(mm) 

 

 

 

25 

30 

35 

111 

132 

193 

126 

201 

Φ

 

The flashover distance, if zero, shall be indicated when ordering. 

 

 

 

Summary of Contents for 100H H8M-100U

Page 1: ...peration Instruction Product Certificate This product has passed the inspections and meets the requirements of GB T 14048 2 and therefore is allowed to leave the factory Inspector Date of inspection S...

Page 2: ...method No code with wiring in front of the plate Code H with wiring behind the plate C for plug in connection and CH for pull out connection only for 3 poles No code for conventional products and cod...

Page 3: ...reaker is suitable for the following working conditions 4 1 The ambient air temperature shall not be higher than 40 C or lower than 5 C 4 2 Altitude 2 000 m 4 3 The relative air humidity shall not exc...

Page 4: ...3 4 3 4 3 3 Rated insulation voltage Ui V AC 600 AC 800 AC 800 Rated impulse withstand voltage Uimp kV 8 Flashover distance mm 50 0 50 0 50 0 Rated ultimate service short circuit breaking capacity Ic...

Page 5: ...50 75 75 100 100 125 125 50 50 75 75 100 100 125 125 Operation performance times Energizing 7 500 7 500 7 500 De energizing 10 000 10 000 10 000 Outline dimensions mm a 140185140180 140 140 2102802102...

Page 6: ...odels see Table 6 Table 6 List of accessory models Shell frame level rated current Inm A 63 100 250 400 630 800 Internal accessories Alarm contact B1 B2 B3 B4 Auxiliary contact F1 F2 F3 F4 Shunt trip...

Page 7: ...of the input terminal of the power supply is AC 50 Hz 230 V 400 V Figure 1 Shunt trip control circuit design 6 4 Parameters of the undervoltage release Rated voltage Ue AC 110 V 230 V 400 V DC 24 V 4...

Page 8: ...MDX1 MDX2 MDX3 MDX4 Rated working voltage Ue V AC 110 V 230 V 50 Hz DC 110V 220 V Starting current A 0 5 2 Operating time S 0 8 Rated operating frequency times h 180 120 Mechanical life times 15 000 9...

Page 9: ...shall be tightened Table 8 Cross section area of the connecting conductor Rated current In A 10 16 20 32 40 50 63 80 100 125 150 160 175 200 225 250 300 350 400 Cross section area of the conductor mm...

Page 10: ...tances the fees for repair still shall be charged even within the warranty period 1 Misuse self modification improper maintenance etc 2 Use beyond the standard specification requirements 3 Falling dam...

Page 11: ...Group Zhejiang High tech Co Ltd Address Wenzhou Bridge Industrial Zone Yueqing City Zhejiang Province Tel 0577 62889999 Fax 0577 62885588 Postal code 325603 http www huyu coin cn Service Hotline 400 8...

Reviews: