www.h-v-c.com
sales@h-v-c.com
Operation and maintenance manual
NCA Series 100 - CE marked fire dampers
NCA Series 100 CE marked fire dampers
Operation and maintenance manual
Page 2 of 2 - Issue A - Issued 24/03/2015
I hereby confirm that the damper detailed above has been tested and
maintained in accordance with the above steps.
Name:
Signature:
Date of inspection:
Operation
Result
Cleanliness
Clean where necessary, ensuring damper is free from dust and debris.
Damage and corrosion
Check for any damage or signs of corrosion to damper components.
Drop test
Confirm operation of damper with a drop test by following the below
steps:
●
Relieve the weight of the blade pack from the fusible link with one
hand placed in the centre of the pack width. Ensure bottom blade
remains parallel to top of damper at all times.
●
Failure to support the blade pack from the centre will result in
damper blades falling unevenly, potentially causing damage to
the damper. In event of damage being caused, damper must be
repaired or replaced. Contact HVC for more information.
●
Remove hand quickly, replicating a splitting fusible link, allowing
damper to shut due to springs / gravity.
●
Perform a visual check of the blades, ensure bottom blade has
latched correctly into both lock guides.
Reset
Reset blade pack by pushing (or pulling if a pull ring is fitted) the
bottom blade off the lock guides and pushing blade pack up into the
header. Reset fusible link correctly.
Confirmation
Confirm that damper has been left in normal working condition.
Maintenance overview and checklist
Fire damper maintenance is essential and should be carried out in
accordance with the requirements set out in:
BS 9999 -
Code of practice for fire safety in the design, management
and use of buildings.
This regulation states that maintenance of air conditioning and
ventilation equipment, including fire dampers is of paramount
importance both in preventing fire and in ensuring that measures taken
to mitigate its consequences are effective when needed.
●
The maintenance steps below should be carried out by a
competent person at least once per year.
●
Local conditions should be taken into consideration when
deciding a test plan, more frequent tests may be necessary. For
example if dusty conditions are prevalent.
●
Series 100 CE marked fire dampers have been designed to
operate without lubrication. Do not introduce any as it will attract
dust and dirt.
Damper reference and location
Μιχαήλ Καραολή 19 143 43, Ν. Χαλκηδόνα, Αθήνα
Τηλ: 211 - 70.55.500 & 210 - 21.30.051, Fax: 210 - 22.23.283