background image

www.h-v-c.com

sales@h-v-c.com

Operation and maintenance manual

NCA Series 100 - CE marked fire dampers

NCA Series 100 CE marked fire dampers

Operation and maintenance manual
Page 2 of 2 - Issue A - Issued 24/03/2015

I hereby confirm that the damper detailed above has been tested and 
maintained in accordance with the above steps.

Name:

Signature:

Date of inspection:

Operation

Result

Cleanliness

Clean where necessary, ensuring damper is free from dust and debris.

Damage and corrosion

Check for any damage or signs of corrosion to damper components.

Drop test

Confirm operation of damper with a drop test by following the below 
steps:

  Relieve the weight of the blade pack from the fusible link with one 

hand placed in the centre of the pack width. Ensure bottom blade 
remains parallel to top of damper at all times. 

  Failure to support the blade pack from the centre will result in 

damper blades falling unevenly, potentially causing damage to 
the damper. In event of damage being caused, damper must be 
repaired or replaced. Contact HVC for more information. 

  Remove hand quickly, replicating a splitting fusible link, allowing 

damper to shut due to springs / gravity. 

  Perform a visual check of the blades, ensure bottom blade has 

latched correctly into both lock guides. 

Reset

Reset blade pack by pushing (or pulling if a pull ring is fitted) the 
bottom blade off the lock guides and pushing blade pack up into the 
header. Reset fusible link correctly.

Confirmation

Confirm that damper has been left in normal working condition.

Maintenance overview and checklist

Fire damper maintenance is essential and should be carried out in 
accordance with the requirements set out in: 

BS 9999 - 

Code of practice for fire safety in the design, management 

and use of buildings.

This regulation states that maintenance of air conditioning and 
ventilation equipment, including fire dampers is of paramount 
importance both in preventing fire and in ensuring that measures taken 
to mitigate its consequences are effective when needed. 

  The maintenance steps below should be carried out by a 

competent person at least once per year.

  Local conditions should be taken into consideration when 

deciding a test plan, more frequent tests may be necessary. For 
example if dusty conditions are prevalent.

  Series 100 CE marked fire dampers have been designed to 

operate without lubrication. Do not introduce any as it will attract 
dust and dirt.

Damper reference and location

Μιχαήλ Καραολή 19 143 43, Ν. Χαλκηδόνα, Αθήνα

Τηλ: 211 - 70.55.500 & 210 - 21.30.051, Fax: 210 - 22.23.283

Reviews:

Related manuals for Airtechnic NCA 100 Series