HVFL Unvented Gas Logs
14
59D1016
INSTALLATION
W
ARNING
Connecting directly to an unregulated
p r o p a n e / L P G t a n k c a n c a u s e a n
explosion.
CHECk GAS PRESSURE
The heater gas inlet connection is a 3/8" NPT at the valve.
On all control type units, the inlet connection is on the right
side of unit. To connect from the opposite side, route the
pipe around the back portion of the unit.
When tightening up the joint to the valve, hold the valve
securely to prevent movement.
Test all gas joints from the gas meter to the heater valve
for leaks using a gas analyzer or soap and water solution
after completing connection.
DO NOT USE AN OPEN
FLAME.
Check the gas pressure with the appliance burning and
the control set to
HIGH
.
MANUAL CONTROL
Figure 16
The pressure regulator is preset and locked to dis-
courage tampering.
If the pressure is not as specified,
replace the regulator with the correct part from the parts
list in this manual.
Remove 1/8" NPT plug, located on side of regulator body.
Install fitting and tubing to pressure gauge. After taking
pressure reading, reinstall test plug. Check for gas leaks.
FP2499
manual valve
NPT Test Plug
FP499
Figure 16 -
Manual Control Pressure
Test Point Location
MILLIVOLT CONTROL
Figure 17
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counter clockwise two or thre turns
and then place tubing to pressure gauge over test point
(Use test point “OUT” closest to control knob). After taking
pressure reading, be sure and turn captured screw clock-
wise firmly to re-seal. Do not over torque. Check for gas
leaks.
FP2372
millivolt valve
Test Port “Out”
FP37
Figure 17 -
Milli-Volt Control Pressure
Test Point Location