background image

HVFL Unvented Gas Logs

38

59D1016

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas fitter 
when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 
detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 
Massachusetts requires the damper to be permanently removed 
or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 
bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 
a T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas fitter 
when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 
bedroom or bathroom regardless of size or type in the State of 
Massachusetts.
Flex line installation must not exceed 36 inches and must have 
a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

() Revise  10.8.3  by  adding  the  following  additional 
requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment installed in every dwelling, building or structure used 
in  whole  or  in  part  for  residential  purposes,  including  those 
owned or operated by the Commonwealth and where the side 
wall exhaust vent termination is less than seven (7) feet above 
finished  grade  in  the  area  of  the  venting,  including  but  not 
limited to decks and porches, the following requirements shall 
be satisfied:
1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 
equipment,  the  installing  plumber  or  gas  fitter  shall  observe 
that a hard wired carbon monoxide detector with an alarm and 
battery  back-up  is  installed  on  the  floor  level  where  the  gas 
equipment is to be installed. In addition, the installing plumber 
or gas fitter shall observe that a battery operated or hard wired 
carbon  monoxide  detector  with  an  alarm  is  installed  on  each 
additional level of the dwelling, building or structure served by 
the side wall horizontal vented gas fueled equipment. It shall be 
the responsibility of the property owner to secure the services of 
qualified licensed professionals for the installation of hard wired 
carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 
hard  wired  carbon  monoxide  detector  with  alarm  and  battery 
back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 
owner shall have a period of thirty (30) days to comply with the 
above requirements; provided, however, that during said thirty 
(30) day period, a battery operated carbon monoxide detector 
with an alarm shall be installed.

Massachusetts Residents Only — Please read and follow these special requirements

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide  detector  as  required  in  accordance  with  the  above 
provisions shall comply with NFPA 70 and be ANSI/UL 034 
listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 
minimum height of eight (8) feet above grade directly in line with 
the exhaust vent terminal for the horizontally vented gas fueled 
heating appliance or equipment. The sign shall read, in print size 
no less than one-half (1/) inch in size, “GAS VENT DIRECTLY 
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 
installation  unless,  upon  inspection,  the  inspector  observes 
carbon monoxide detectors and signage installed in accordance 
with the provisions of 48 CMR 5.08()(a)1 through 4.
(b) 

Exemptions:

 The following equipment is exempt from 48 

CMR 5.08()(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 
Required To Be Vented" in the most current edition of NFPA 54 
as adopted by the Board; and
.  Product Approved  side  wall  horizontally  vented  gas  fueled 
equipment  installed  in  a  room  or  structure  separate  from  the 
dwelling,  building  or  structure  used  in  whole  or  in  part  for 
residential purposes.
(c)  

Manufacturer  requirements  —  Gas  Equipment  Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 
a  venting  system  design  or  venting  system  components  with 
the  equipment,  the  instructions  provided  by  the  manufacturer 
for installation of the equipment and the venting system shall 
include:
1. Detailed instructions for the installation of the venting system 
design or the venting system components; and
. A complete parts list for the venting system design or venting 
system.
(d) 

Manufacturer requirements — Gas Equipment Venting 

System  Not  Provided. 

When  the  manufacturer  of  a  Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 
does  not  provide  the  parts  for  venting  the  flue  gases,  but 
identifies “special venting systems,” the following requirements 
shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 
be  included  with  the  appliance  or  equipment  installation 
instructions; and
. The “special venting systems” shall be Product Approved by 
the Board, and the instructions for that system shall include a 
parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 
all  venting  instructions,  all  parts  lists  for  venting  instructions, 
and/or all venting design

Summary of Contents for 18HVFL

Page 1: ...neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agen...

Page 2: ...E USING THE APPLIANCE IMPORTANT Read all instructions and warnings carefully before starting installation Failure to follow these instructions may result in a possible fire hazard and will void the wa...

Page 3: ...area of firebox Ceiling fans may create drafts that alter burner flame patterns Sooting and improper burning will occur 14 Caution Candles incense oil lamps etc produce combustion byproducts includin...

Page 4: ...er Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water 24 This appliance must not be...

Page 5: ...um of 13 0 w c for LP systems ignition controls Piezo ignitor allows ignition of the pilot without the use of matches or batteries Manual control has three 3 positions OFF All gas to the gas logs is s...

Page 6: ...t sensor Carefully inspect the contents for shipping damage If any parts are missing or damaged immediately inform the dealer from whom you purchased the appliance Do not attempt to install any part o...

Page 7: ...ealed b weather striping has been added on openable windows and doors and c caulking or sealants are applied to areas such as joints around window and door frames between sole plates and floors betwee...

Page 8: ...cs of the fireplace which in turn can cause the unit to overheat and malfunction WARNING Important information for the installation of this gas log set The following are guidelines for placing a gas l...

Page 9: ...logs into a fireplace with no wooden mantel shelf or other combustible projection above the fireplace opening measure the heat resistant material height per Figure 5 then see TABLE A Heat resistant ma...

Page 10: ...ast 12 and observe material to at least 12 profiles shown on Page 15 and observe profiles Fig 7 shown on Page 16 Fig 9 Less than 8 Extend heat resistant mat l Extend heat resistant to at least 8 insta...

Page 11: ...mum acceptable distance of 6 If your mantel profile is unsafe you may either Raise the mantel to an acceptable height or Remove the mantel 1 6 Minimum FP2801 combustible floor Heater in Fireplace or F...

Page 12: ...sote or other obstructions Have this cleaning performed annually after installation Seal any fresh air vents or ash clean out doors located on floor or wall of fireplace If not drafting may cause pilo...

Page 13: ...used per National Fuel Code section 2 6 3 providing gas meets hydrogen sulfide limits and where permitted by local codes Gas piping system must be sized to provide minimum inlet pressure Listed on Dat...

Page 14: ...ulator is preset and locked to dis courage tampering If the pressure is not as specified replace the regulator with the correct part from the parts list in this manual Remove 1 8 NPT plug located on s...

Page 15: ...s can cause improper and dangerous operation Verify proper operation after servicing WARNING The milli volt valve is a self powered combination gas control that does not require 110 Vac to oper ate Co...

Page 16: ...ry life You can protect the receiver and extend battery life by mounting the receiver in a wall or other location outside the fireplace FP2813 remote receiver Remote Wire Con nectors Remote Receiver F...

Page 17: ...two 2 0 250 male spade terminals for remote or t stat option Figures 22 and 23 7 Install knob to shaft of t stat sensor Figure 22 8 Place thermo bulb in front of the firebox for incoming air HIGH LOW...

Page 18: ...millivolt meter hav ing a 1 1000 mV range Conduct each check shown in chart by connecting meter test leads to terminals as indicated A Complete Millivolt System Check A Reading Thermostat contacts CLO...

Page 19: ...these logs with your bare hands Always wear gloves to prevent skin irritation from ceramic fibers After handling the logs wash your hands gently with soap and water to remove any traces of fibers Pla...

Page 20: ...Cluster 3 Pins LG956 LG957 HVFL SH top center log Top Center Log 4 LG957 Figure 29 2 Place left log cluster 2 on pin located near left edge of base Figure 27 3 Place right log cluster 3 on two pins l...

Page 21: ...stability Figure 30 2 Place right bottom log 2 on two 2 pins located on right side of base Figure 31 LG958 HVFL SP back log Rear Log 1 Pins LG958 Figure 30 LG959 HVFL SP right bottom log Right Bottom...

Page 22: ...g 6 LG962 Figure 34 4 Rest back end of top middle log 4 on rear log and place front end of top middle log 4 on bottom right and left logs Figure 33 5 Place top right back log 5 on right bottom log and...

Page 23: ...e present when the heater is in operation It should just touch the top of the thermocouple tip for natural Refer to Figure 35 for correct pilot flame If the pilot flame does not touch the thermocouple...

Page 24: ...Figure 37 Seasoned Hardwood Correct Rear Flame Appearance Figure 38 Stacked Pine Correct Rear Flame Appearance LG963 LG964 The left and right rear flames should be yellow and extend 1 2 above the mid...

Page 25: ...e chemicals are not harmful but may produce annoy ing smoke and smells as they are burned off during the initial operation of the appliance possibly causing headaches or eye or lung irritation This is...

Page 26: ...tions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t tr...

Page 27: ...release the piezo ignitor button to light the ODS pilot The pilot is located on the left side of the heater behind the middle log and in front of the back log If piezo ignitor does not light the pilo...

Page 28: ...gas control knob counterclockwise to IGN position Push in control knob for 5 seconds 7 With the control knob pushed in push in and release the piezo ignitor button to light the pilot 8 Continue pushin...

Page 29: ...diagram for location of items discussed below Do not use cleaning fluid to clean logs or any part of heater Brush logs with soft bristle brush or vacuum with brush attachment Vacuum loose particles a...

Page 30: ...utoff valve closed 2 Control knob not in PILOT position 3 Control knob not pressed in while in PILOT position 4 Air in gas lines when installed 5 ODS pilot is clogged 6 Gas regulator setting is not co...

Page 31: ...clogged or dam aged 2 Burner is damaged 3 Gas regulator is defective 1 Vapors from paint or curing process of logs 1 Turning control knob to HIGH posi tion when burner is cold 2 Air in gas line 3 Dir...

Page 32: ...2 5 Manual 6 10 11 11 3 4 13 9 5 Millivolt 12 591015 HVFL parts WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this ap...

Page 33: ...11 Control Knob 1 18D0603 18D0603 18D0603 18D0603 Millivolt Control 5 Control Valve 1 14D0467 14D0468 14D0467 14D0468 8 Front Burner Injector 1 59D2008 59D2010 59D2012 59D2014 9 Rear Burner Injector...

Page 34: ...or failure to use only parts specifically approved with this appliance may result in property damage or personal injury Seasoned Hardwood Logs Ref Description Qty 18HSHCL 24SHCL 30SHCL 1 Back Log 1 5...

Page 35: ...Qty 18SPRL 24SPRL 30SPRL 1 Back Log 1 59D1300 59D1307 59D1314 2 Right Bottom Log 1 59D1301 59D1308 59D1315 3 Left Bottom Log 1 59D1302 59D1309 59D1316 4 Top Middle Log 1 59D1305 59D1312 59D1319 5 Top...

Page 36: ...HVFL Unvented Gas Logs 36 59D1016...

Page 37: ...HVFL Unvented Gas Logs 59D1016 37...

Page 38: ...ith the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please read...

Page 39: ...nty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by acc...

Page 40: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: