Poseidon2
– Family manual
HW group
www.HW-group.com
99 / 104
OID descriptions of SNMP variables
The following table lists the variables, their OID addresses and values. The values apply to the
specified Poseidon configuration shown in the HTML page screen shot on the right.
Firmware:
1.9.6
Dry contact states: 1=ON, 2=Off, 3=Off, no alarms
Connected sensors:
1x HTemp-485
(1x temperature [ID 80], 1x humidity [ID 112])
1x 1Wire bus
(temperature [ID 50176, 47872])
Variable
OID
Value
Description
sysDescr
.1.3.6.1.2.1.1.1
.iso.org.dod.internet.mgmt.mib-2.system.sysDescr
Poseidon SNMP
Supervisor v1.9.6
Textual description of the
entity
sysUpTime
.1.3.6.1.2.1.1.3.0
.iso.org.dod.internet.mgmt.mib-2.system.sysUpTime
0:17:12:32.18
Time (in tens of
milliseconds) since the last
init of the network
management portion of the
system
Input 1 state
.1.3.6.1.4.1.21796.3.3.1.1.2.1
*).inpTable.inpEntry.inpState
On (2)
Binary input states (integer)
Input 3 state
.1.3.6.1.4.1.21796.3.3.1.1.2.3
*).inpTable.inpEntry.inpState
Off (1)
Input 2 Name
.1.3.6.1.4.1.21796.3.3.1.1.3.2
*).inpTable.inpEntry.inpName
Binary 2
Binary input name (string)
Input 3 Alarm
.1.3.6.1.4.1.21796.3.3.1.1.4.3
*).inpTable.inpEntry.inpSetupAlarm
No (0)
Alarm for the binary input,
generated by the device
under defined conditions
RTS Output
(Port 2)
.1.3.6.1.4.1.21796.3.3.2.1.2.2
*).outTable.outEntry.outState
Off (1)
Binary input state (integer)
Sensor 1 Name
.1.3.6.1.4.1.21796.3.3.3.1.2.1
*).tempTable.tempEntry.sensorName
HTemp temp
Sensor name (string)
Sensor 1 State
.1.3.6.1.4.1.21796.3.3.3.1.4.1
*).tempTable.tempEntry.sensorState
normal (1)
Binary input states (integer)
Sensor 2 State
.1.3.6.1.4.1.21796.3.3.3.1.4.2
*).tempTable.tempEntry.sensorState
alarm (2)
Sensor 1 Value
.1.3.6.1.4.1.21796.3.3.3.1.6.1
*).tempTable.tempEntry.tempValue
223
Integer (decimal * 10)
representation
of the temperature (integer)
Sensor 2 Value
.1.3.6.1.4.1.21796.3.3.3.1.6.2
*).tempTable.tempEntry.tempValue
223
Sensor 4 Value
.1.3.6.1.4.1.21796.3.3.3.1.6.4
*).tempTable.tempEntry.tempValue
223
Sensor 2 Name
.1.3.6.1.4.1.21796.3.3.99.1.2.1.2.2
*).setup.tempSetup.tempSetupTable.tempSetupEntry.tempSensorName
HTemp humid
Sensor name (string)
Sensor 1 ID
.1.3.6.1.4.1.21796.3.3.99.1.2.1.4.1
*).setup.tempSetup.tempSetupTable.tempSetupEntry.tempSensorAddr
80
Unique sensor ID (integer)
*)
Text version of the OID begins with “.iso.org.dod.internet.private.enterprises.hwgroup.charonII.poseidon” which corresponds to the numerical OID
“.
1.3.6.1.4.1.21796.3.3
”.