Type plate and serial number

The insert comes with type plate and serial number on the inside of the outer casing:

Locate the unique serial number of your insert and make a note of it below so that it is always easily accessible. The serial number must always 
be provided when contacting your HWAM retailer.

Serial number (starts with “F4”): 

Floor plate

European, national and local regulations must be observed in terms of the size and thickness of a non-combustible floor covering the floor in front 
of the combustion chamber opening. Ask your HWAM retailer for assistance. The combustion chamber opening is 62.7 cm wide.

Requirements for chimney and flue duct

The height of the chimney must ensure sufficient draught and prevent any smoke nuisance. As a general rule, satisfactory draught conditions are 
achieved if the chimney is 4 m above the stove and at least 80 cm above the ridge. If the chimney is placed at side walls, the top of the chimney 
should always be higher than the ridge or the tallest point of the roof. Always be aware of any national and/or local regulations applying to thatched 
roofs and the location of the chimneys. 

The insert requires a minimum draught of 12 Pa (measured at EN 13229 measurement point). If measured just above the smoke flue socket, the 
chimney draught must be 18-20 Pa.

The chimney must have a minimum clearing of Ø 150 mm. The chimney must be provided with an easily accessible cleaning door. The chimney and 
flue duct must be of flue class T400 and be CE marked. Furthermore, it must have obtained the classification of G in soot fire testing. The required 
distance to combustible material must be complied with in accordance with the brand label. Ask your HWAM retailer for further information.

I

NSTALLATION

 

AND

 

CONNECTION

 

In general

HWAM I 40/55 consists of a separate outer casing as well as a separate insert that is pushed into place and connected when the outer casing 
has been properly installed. We recommend installing a fresh air system that provides external air directly to the combustion (may be purchased 
separately as an accessory). A fan kit that will improve heat utilisation and heat distribution in the room can also be purchased as an accessory. 
The outer casing comes with 2 pre-cuts for the connection of tubes for the distribution of convection heat to other rooms.

Installation in rooms with non-combustible material

If the insert is installed in rooms where there is no combustible material, we recommend a distance between masonry and the outer casing of 
5 mm as a minimum. This should prevent the brickwork from cracking when the outer casing expands during use. The masonry above the casing 
must therefore be load bearing. 

Installation in rooms with combustible material

If the insert is installed adjacent to combustible walls, a ventilated installation of non-combustible material such as calcium silicate or other mate-
rial with a thermal conductivity (EN 12667 @ 10 °C) of less than 0.068 W/m x K must be built. Requirements for this installation appear from 
the illustrations in this installation guide.

Vent holes

The illustrations show minimum areas for vent holes. The area can be distributed on several vent holes. If the area is distributed on more than 2 
vent holes for lower and upper holes respectively, the total area must be increased to compensate for a higher pressure loss. If grates are mounted 
in the vent holes, the total vent hole area must be increased to compensate for the additional pressure loss caused by the grates. 

EAN

S.nr.:

EN 13229:2001 / 
A1:2003 / A2:2004
Inset appliances 
fired by solid fuel

HWAM A/S

Nydamsvej 53 - DK 8362 Hørning

Tel.: (+45) 86 92 18 33

Fax: (+45) 86 92 22 18

HW

N
DK

Brensel

ved

Partikulær utslipp 

1,87 g/kg

Prøvningsinstitutt

NB 1235

Prøvningsrapport            

300-ELAB-2471-NS

NS 3058 

NS 3059

HWAM I 40/55 IHS

 

  

20

Room-air independent fireplace type:

FC

61x 

DIBT approval number

in preparation

Test report

300-ELAB-2471-RU

In connection with ambient air independent operation, combination or multiple 
outlet is not allowed.
Read and follow the user

s manual carefully. 

Use only recommended fuel.

Thermal output:

6.0 kW

Fuel types

wood

Combustible materials 

– 

minimum distance to non-combustible insulation:

- Side  

50 mm

- Behind  

50 mm

Information about insulation and other dimensions see installation instructions
Distance to furnishings front

1200 mm

CO Emission at 13% O

2

0.077 %  / 963 mg/m

3

Particles at 13% O

2

16 mg/m

3

Energy effiency

83 %

Flue gas temperature EN 13229 measurement point

251 °C

Flue gas temperature measured in the outlet socket

299 °C

Laboratory registration number

NB 1235

Test report     

300-ELAB-2471-EN

The appliance is capable of intermittent operation.
The appliance can be used in a shared flue.
Follow the user

s manual and use only recommended fuel.

Declaration of Performance:  www.hwam.com/dop/i40-55

Norm Österreich 15a B-VG                                   

300-ELAB-2471-AUS

Thermal output:

6.0 kW

Energy effiency

83 %

CO

553 mg/MJ

Particles

10 mg/MJ

NO

x

59 mg/MJ

OGC

12 mg/MJ

15A

Summary of Contents for I 40/55

Page 1: ...Installation instructions EN I 40 55 20 10 2021 97 9696 www hwam com ...

Page 2: ......

Page 3: ...pe plate and serial number 6 Floor plate 6 Requirements for chimney and flue duct 6 INSTALLATION AND CONNECTION 6 In general 6 Installation in rooms with non combustible material 6 Installation in rooms with combustible material 6 Built in example 7 Installation instructions 10 Product information EcoDesign 18 ...

Page 4: ...y be bought separately Before installing the insert make sure that the floor can carry the insert the chimney and any other parts required for the installation Remember to consider that the stove must be connected to power Please be aware that not all glass parts are heat resistant For this reason a glass wall should sometimes be treated as a flammable wall in which case we ask you to contact your...

Page 5: ...744 396 543 306 266 290 Page 1 of 2 CAD 0193030 Created nis 18 12 2019 01 Comment Init Date Rev Frigivet nis 18 12 2019 A nis 18 12 2019 DS EN 22768 m 1 10 A4 ased Created date Item number kg Tolerance HWAM A S Nydamsvej 53 55 DK 8362 Hørning Tel 45 86 92 18 33 Fax 45 86 92 22 18 Created by Configuration name Item Drawing number Model Hwam I 40 55 IHS målskitse firkant mm A Min 70 Min 140 Min 295 ...

Page 6: ...ible material If the insert is installed in rooms where there is no combustible material we recommend a distance between masonry and the outer casing of 5 mm as a minimum This should prevent the brickwork from cracking when the outer casing expands during use The masonry above the casing must therefore be load bearing Installation in rooms with combustible material If the insert is installed adjac...

Page 7: ...350 SECTION C C Convection opening min 500 cm Floor SECTION E E Distance from furniture to glass pane Combustible material Fire wall min 50 mm Calcium Silicate Insulated chimney UK Hwam I40 55 sikkerh Sheet1 A 27 05 2019 nis Frigivet Frigivet nis 27 05 2019 B Comm Init Date Rev Frigivet nis 10 10 2019 C nis 27 05 2019 3891 81 1 15 A3 CAD 0190810 Com Released Created date Format kg Part Weight Tole...

Page 8: ...in 500 cm Floor SECTION E E Distance from furniture to glass pane Combustible material Fire wall min 50 mm Calcium Silicate Insulated chimney UK Hwam I40 55 sikkerh Sheet1 A 27 05 2019 nis Frigivet Frigivet nis 27 05 2019 B Comm Init Date Rev Frigivet nis 10 10 2019 C nis 27 05 2019 3891 81 1 15 A3 CAD 0190810 Com Released Created date Format kg Part Weight Tolerance HWAM A S Nydamsvej 53 55 DK 83...

Page 9: ...mbustible material Fire wall min 50 mm Calcium Silicate Insulated chimney UK Hwam I40 55 sikkerh Sheet1 A 27 05 2019 nis Frigivet Frigivet nis 27 05 2019 B Comm Init Date Rev Frigivet nis 10 10 2019 C nis 27 05 2019 3891 81 1 15 A3 CAD 0190810 Com Released Created date Format kg Part Weight Tolerance HWAM A S Nydamsvej 53 55 DK 8362 Hørning Tel 45 86 92 18 33 Fax 45 86 92 22 18 Material Created by...

Page 10: ...the installation of fans and fresh air system must have been completed Polystyrene from packaging may be placed on the floor and serve as protection for the insert when it is lifted out of the casing Note It isVERY important to secure the outer casing to the support with screws Otherwise it may fall out during servicing when the insert is turned out of the casing 1 2 3 4 ...

Page 11: ...Page 11 of 20 pages 5 6 7 ...

Page 12: ...Page 12 of 20 pages 8 9 10 ...

Page 13: ...Page 13 of 20 pages 13 12 11 ...

Page 14: ...Page 14 of 20 pages 16 15 14 ...

Page 15: ...Page 15 of 20 pages 19 18 17 ...

Page 16: ...Page 16 of 20 pages 21 22 20 ...

Page 17: ...Page 17 of 20 pages 24 25 23 ...

Page 18: ...ems in a way that is as sustainable as possible and that is in line with the current environmental protection reprocessing recycling and disposal technology Useful efficiency at nominal heat output 83 Energy efficiency index 110 Energy efficiency class A Electric power consumption nominal heat output kW 0 015 Electric power consumption minimum heat output kW 0 012 Electric power consumption standb...

Page 19: ...Page 19 of 20 pages ...

Page 20: ......

Reviews: