Instructions for connection of a stove
with domestic water heating
The mounting and installation of an HWAM stove with domestic water heating must follow
DIN 4751, page 2:
1. This kind of heat generators is only permitted to be used with a kettle temperature not
higher than 90°C.
2. The heat exchanger is not permitted to be used for the purpose of heating the domestic
water.
3. The flow pressure available for heating the domestic water must account for at
least 2 atmospheric pressures. If the water conduit falls down under 2 atmospheric
pressures, for example at power failure by your own water supply and at failure
by the circulating pump, then the kettle must immediately be taken out of function.
4. Between the domestic water supply and the thermal drain securities no delimiter of the
flow mass must be installed.
5. As thermal drain security only a certified unit is allowed to be used, fulfilling the following
demands:
•
Response temperature 95°C.
•
Flow rate with a sensor temperature of 110°C and a differential pressure at the thermo
valve of 1 atmospheric pressure must be at least 200 kg per hour.
•
The procurement as well as the proper fitting of the required thermo valve is the respon-
sibility of the installation firm.
6. The maximum transport pressure in the joint piece is not permitted to exceed 2,5 mmWS.
If this value is exceeded on the assembly place, then the chimney must be provided with
a shunt appliance.
7. The equalization vessel must be equipped at its highest point with an automatically func-
tioning exhaust valve.
Furthermore, when you fire with solid fuel you have to pay special attention to the following
points:
a. The water pressure in front of the thermal drain security must account for at least 2 atmo-
spheric pressures, also at open thermal valve.
b. It obliges the user to let a competent person control the thermal drain security at least once
a year. At this occasion the scales and the slop, if any, should be removed from the thermal
drain security. The thermal valve must in this connection be tested on its functionality.
Important!
The heat connection must always be done by a specialist (heating constructor). Only he knows
how to connect the water-leading heat kettle of the stove in a skilled way and according to
the DIN norms.