34
EDS
3000
IO-Link
Stand: 20.04.2020
HYDAC
ELECTRONIC
GMBH
Mat. Nr.: 669897
Variable "BDC1 Thresholds" index=60 id=V_Bdc1Thresholds
data type: 32-bit Record (subindex access not supported)
access rights: rw
modifies other variables
excluded from data storage
subindex
bit
offset
data type
allowed
values
default
value
mod. other var.
name
description
1
16
16-bit Integer
See
10.2
156
V_PrimaryValueSp1 Setpoint SP1
Lower limit of
RP / FL in bar
2
0
16-bit Integer
See
10.2
313
V_PrimaryValueSp1 Setpoint SP2
Upper limit of
SP / FH in bar
SP = switch point RP = switch-back point FL = pressure window lower value FH = pressure window upper value
octet
0
1
2
3
bit offset
31 - 24
23 - 16
15 - 8
7 - 0
subindex
1
1
2
2
element bit
15 - 8
7 - 0
15 - 8
7 - 0
Variable "BDC1 Behavior" index=61 id=V_Bdc1Behavior
data type: 32-bit Record (subindex access not supported)
access rights: rw
modifies other variables
excluded from data storage
subindex
bit
offset
data type
allowed
values
default
value
mod. other var.
name
description
1
24
8-bit UInteger
0 = Default, 1
= Inverted
0
V_PrimaryValueSp1
Switch Point
Logic
NO/NC
2
16
8-bit UInteger
2 = Window,
3 = Two-Point
3
V_PrimaryValueSp1
Switch Point
Mode
3
0
16-bit
UInteger
0
V_PrimaryValueSp1
Switch Point
Hysteresis
octet
0
1
2
3
bit offset
31 - 24
23 - 16
15 - 8
7 - 0
subindex
1
2
3
3
element bit
7 - 0
7 - 0
15 - 8
7 - 0
Standard Variable "Device Access Locks" index=12 id=V_DeviceAccessLocks
data type: 16-bit Record (subindex access not
supported)
access rights: rw
subindex
bit offset
data type
name
description
1
0
Boolean
Parameter (write)
Access Lock
2
1
Boolean
Data Storage Lock
Datenhaltung (Subindex 2) ist aus
Kompatibilitätsgründen vorhanden und sollte immer auf
„False“ stehen, um unerwartetes Verhalten beim Data
Storage zwischen Master und Gerät zu vermeiden.
3
2
Boolean
Local
Parameterization
Lock
4
3
Boolean
Local User Interface
Lock
For compatibility reasons only – it is
recommended to keep subindex 2 „false“ in
order to avoid any unwanted system
behavior if data storage is set via IO-Link
master.