EDS 3000 IO-Link
9
Edition: 20.04.2020
HYDAC
ELECTRONIC
GMBH
Part no.: 669897
ATTENTION
Installation of the EDS 3000 must be carried out using a spanner (AF 27)
suiting the hexagonal nut of the pressure port.
Inappropriate installation methods, such as manually fitting above the
housing can damage the housing or even cause the device to fail
completely, due to the rotatability of the EDS 3000.
CAUTION !
6.2 Additional installation instructions
Additional installation instructions which, from experience, reduce the effect of
electromagnetic interference:
Make line connections as short as possible.
Use shielded cabling (e.g. LIYCY 4 x 0.5 mm²).
The cable shielding must be fitted by qualified personnel, subject to the
environmental conditions and with the aim of suppressing interference.
Keep the instrument well away from the electrical supply lines of power equipment, as
well as from any electrical or electronic equipment causing interference.
7
Control elements of the EDS 3000
The and arrow keys serve to select the desired menu item and to set the values.
•
One step back in menu
•
Reduce value
•
Ascend in the menu
•
Increase value
Display of
Pressure unit
4-digit
Digital display
LED-Display of
the active switch point
Buttons for setting
Switch points, switch-back points
and additional functions
LED display constantly lit: Switch in SIO mode LED display
flashing: Switch in SDCI mode