ETS 4100S IO-Link
11
Edition: 2020-07-20
HYDAC ELECTRONIC GMBH
Part no.: 670032
E
o
Mode (Subindex 2): Switching function: Default: Deactivated
- Deactivated:
The SSC is always OFF.
-
Single-Point / Hysteresis:
In the single point mode the parameters SP1 and Hyst are used.
If the measured value reaches or exceeds the switching point SP1, the
SSC will switch to ON.
If the measured value falls below the switch back point SP1 – Hyst, the
SSC will switch to OFF.
SSC → ON,
if measured value ≥ SP1
SSC → OFF,
if measured value < SP1 - Hyst
-
Window mode:
In the window mode the parameters SP1, SP2 and Hyst are used.
If the measured value stays within the window [SP2, SP1], the SSC will
switch to ON.
If the measured value falls below the lower window frame SP2 – Hyst,
the SSC will switch to OFF.
If the measured value rises over the upper window frame SP1 + Hyst,
the SSC will switch to OFF.
SSC → ON,
if SP2 ≥ measured value ≥ SP1
SSC → OFF,
if measured value < SP2 - Hyst or
measured value > SP1 + Hyst