ETS 4100S IO-Link
13
Edition: 2020-07-20
HYDAC ELECTRONIC GMBH
Part no.: 670032
E
o
Switching delay (Subindex 5):
Switching delay in ms for switching into the active condition.
o
Switch-back delay (Subindex 6):
Switch-back delay in ms to switch in to the inactive condition.
10.5 Device information and diagnostic options (read only)
The new generation of smart sensors detects further relevant information in addition to the
operation data.
Name of manufacturer (Index 16):
HYDAC ELECTRONIC GMBH
Product name (Index 18):
Type designation, i.e. ETS 4146S-F31-100-000
Product ID (Index 19):
Part number, i.e. 928313
Serial number (Index 21)
Hardware version (Index 22)
Firmware version (Index 23)
Error counter (Index 32)
Device status (Index 36):
- (0) Device is OK
- (1) Maintenance required
- (2) Beyond specification
- (3) Function test
- (4) Error
- (5..255) Reserved
Detailed device status (Index 37):
Process data input (Index 40))
Temperature (Index 112):
Process values of the temperature since reset. Reset is
possible using standard command 164.
o
Current measured value (Subindex 1):
Current temperature value (filtered) in °C with 1 decimal place.
o
Minimum measured value (Subindex 2):
Minimum temperature value (filtered) in °C with 1 decimal place.
o
Maximum measured value (Subindex 3):
Maxmum temperature value (filtered) in °C with 1 decimal place.
Device temperature (Index 127):
Process values of the device temperature since
reset. Reset using standard command 164.
o
Current measured value (Subindex 1):
Current device temperature value in °C with 1 decimal place.
o
Minimum value (Subindex 2):
Minimum device temperature value in °C with 1 decimal place.
o
Maximum value (Subindex 3):
Maximum device temperature value in °C with 1 decimal place.
Lifelong operating times (Index 256):
Device operating times from delivery on, i.e.
over the device's entire life cycle
o
Operating hours (Subindex 1):
Operating times in h
o
Arrhenius value device (Subindex 2):`
Arrhenius value device in h, corresponds with the amount of hours at a device
temperature of 20 °C. Arrhenius value is a temperature compensated
operating time.