Electrical connection of the CMP
CMP1000
en(us)
Page 28 / 44
MoWa CMP 3528418d en-us 2015-01-06.doc
2015-01-06
Electrical connection of the CMP
DANGER
Exposed electrical components in the switch
cabinet
Danger of fatal injury due to electric shock
►
Any work involving the electrical system may
only be done by a properly trained, certified
electrician.
Compare the voltage and frequency specifications on the type label with the
specifications for the available network.
The pump motor must be protected from overloading, in accordance with
VDE 0113.
Check the direction of rotation of the motor by switching it on briefly (jog
mode). The rotational direction is indicated by an arrow on the fan cover.
To change the direction of rotation, commutate two phases.
Depending on the network voltage, connect the motor in a star or delta
connection. Check the type label on the motor to accomplish this.