Safety precautions
LVU-CD-40 /-T001
en(us)
Page 10 / 52
BeWa LVU-CD-40-T001 4142242a en-us 2016-05-13.doc
2016-05-13
Proper/Designated Use
Use the unit only for the application described in the following.
The LowViscosity Unit LVU is used for two-stage offline filtration, with solid
particle contamination and free water being removed from diesel fuel. The
degree of water separation is > 95 % as per ISO CD 16332 and the
dewatering rate is 50 l/h at 5 % water in the diesel. The limit of application is
obtained at a maximum of 10 % free water.
DANGER
Unacceptable fluid temperature
Risk of bodily injury due to burns
►
Observe the maximum fluid temperature of <
50°C and at least 10°C below the flash point
of the fluid used.
DANGER
Dry running of the pump
Risk of bodily injury due to burns
►
Ensure that the pump does not run dry.
NOTICE
Impermissible operating media.
The unit will be destroyed.
►
The unit may only be used in combination with diesel, biodiesel
B0 … B100 or fuel oil.