Unit setup/connection
LVU-CD-40 /-T001
en(us)
Page 27 / 52
BeWa LVU-CD-40-T001 4142242a en-us 2016-05-13.doc
2016-05-13
Connecting the water outlet
Connect the water outlet to a depressurized reservoir without cross-section
reduction. Reservoir height max. 1.5 m and no higher than the fluid level in
the tank.
The separated water can contain some parts of fuel.
Dispose of the water-fuel mixture in an environmentally
friendly manner.
NOTICE
Excess pressure at the water outlet
The unit will be damaged
►
Guide the water outlet into a depressurized reservoir.
Electrical connection of the unit
The filtration unit has a main switch with motor protection, connector cable
with a power plug. Connect the electric motor to the terminal box of the
electrical motor for right-hand rotation.
DANGER
Exposed electrical terminals in the terminal
box on the electric motor
Danger of fatal injury due to electric shock
►
Any work involving the electrical system may
only be done by a properly trained, certified
electrician.
Unwind the connector cable fully. Plug the power plug into a suitable,
earthed, protected power outlet. Match the specifications for the power
supply and frequency on the unit with the network specifications.