Unit setup/connection
OXiStop OXS
en
Page 34 / 108
MoWa OXS 3992763e en-us 2018-08-10.docx
2018-08-10
Electrical connection of the heat exchanger's electric motor (optional)
DANGER
Exposed electrical components in the switch
cabinet
Risk of fatal injury from electrocution
►
Any work involving the electrical system may
only be done by a properly trained, certified
electrician.
Compare the voltage and frequency specifications on the unit name plate
with the existing network specifications.
Check the direction of rotation of the electric motor by switching it on briefly
(jog mode).
NOTICE
Incorrect phase sequence / rotation direction of the electric motor
The pump will be destroyed
►
In jog mode, check the direction of rotation of the electric motor.
►
A rotation direction arrow on the fan cover of the electric motor
identifies the correct direction of rotation.