Control panel basic (SIMATIC PANEL)
FluidAqua Mobil - FAM10/15-P
en(us)
Page 61 / 124
BEWA FAM10-15-P 4052078 en-us 2015-11-05.doc
2015-11-05
Operating mode - Dewater to / Filter to
The operating mode "Filter to" is possible only up to a relative humidity of
90%. The CS is switched off in situations involving >90% or unmanaged
water.
The following message is output when the contamination menu is selected:
"Oil saturation >90%. Measurement with CS not possible!"
You can switch off this display by pressing the ESC key, so that you can exit
the screen again by selecting Menu1.
If a water saturation level of
≥
90% occurs during automatic operation, then
the operating mode switches automatically in accordance with the following
table:
Selected operating mode:
changes automatically after:
FTT
=>
FT
EW+FTB
=>
DW+FT
EW+H+FTB
=>
EW+H+FT
H+FTT
=>
H+FT
The limit values for "Dewater to" are to be set in the RH+P screen, the limit
values for "Filter to" in the CONT. screen.
Once the limit values have been reached, the FAM stops automatically. After
the set test interval has expired, the FAM starts automatically. If the
measured values still fall below the set limit value after 2 minutes, the the
FAM will switch off automatically and the testing interval will start again.