Error messages / Troubleshooting
FluidAqua Mobil - FAM10/15-P
en(us)
Page 90 / 124
BEWA FAM10-15-P 4052078 en-us 2015-11-05.doc
2015-11-05
3. FAM outlet is blocked
Cause:
The level must reach the MIN switch point within 5
minutes once the MAX switch point in the vacuum
column has been reached.
Remedy: Perform
the
following
steps:
Step
Description
1.
Message:
3. FAM outlet is blocked
2.
Check all of the locking devices in the return line for flow.
3.
Actuate ESC key and reset failure with the F3 key.
4.
Start the unit by pressing the F1 key.
->a. The fault is repeated.
-> proceed to Step 6.
5.
->b. The fault is not repeated.
-> proceed to Step 11.
6.
Check the evacuation pump for proper functioning.
Check the return valve.
Check the suction line for constrictions.
Check the filter for flow.
7.
Actuate ESC key and reset failure with the F3 key.
8.
Start the unit by pressing the F1 key.
->a. The fault is repeated.
-> proceed to Step 10.
9.
->b. The fault is not repeated.
-> proceed to Step 11.
10.
Contact the HYDAC service department.
11.
The fault is repaired.