Description of CANopen-Interface
HYDAC ELECTRONIC GMBH
07.10.2010
Mat. No. 669824
Page 60 of 63
12 Causes of faults and remedies
12.1 SDO Error codes
In the case of an error (SDO response CCD = 0x80) the data field contains a 4-byte
error code. By the measuring system the following error codes are supported:
Error code Meaning
Remedy
0x0600 0006
EEPROM error
Possibly shut-off measuring system voltage then
switch on again. If the error recurs despite this
measure, the measuring system must be replaced.
0x0601 0000
Unsupported access to an object
Check which attribute for the corresponding object is
valid:
- rw: read- and write access
- wo: write only access
- ro: read only access
- Const: read only access
0x0609 0011
Sub-index does not exist
Check which sub-indices the corresponding object
supports.
0x0800 0000
General error
Wrong signature written when storing the parameters,
see Object 1010h: Store parameters, page 46.
Table 10: SDO Error codes
12.2 Emergency Error codes
Emergency objects are triggered by the occurrence of a device internal error
situation, transmission format see chapter “Emergency Message”, page 57.
The error indication is carried out about the objects
-
Error register 0x1001, page 43 and
-
Pre-defined error field 0x1003, page 44