Status LED / Causes and remedies
Status LED
Cause(s)
Remedy
LED flashing green
The main switch is
on, but the unit was
switched off via
remote stop.
The interval control
is active and the
timer is running
until it is next
switched on.
Detailed information can be
found at the selectors interval
control, see page 34 and time
selector switch, see page 35.
If the selector switch for the
interval control is not set to
or
, then the
timer set at the selector switch's
time selector switch is active.
If the interval control selector
switch is set to
, the unit
was switched off via remote stop.
The unit can be switched on or
off with the main switch.
If the selector switch for the
interval control is set to
,
then the operation has switched
off once according to the setting
of the selector switch's time
selector switch.
LED continuous
green light
The main switch is
on and the unit is
running.
No remedy is required.
LED continuous
yellow light
The main switch is
on, but the unit is
not running.
Error "Entry
blocked" The level
"Drainage level
reached" was not
exceeded during
the first six minutes
after activation.
Check the inlet and open it if
necessary. Then switch off the
unit at the main switch and
switch it back on again. If the unit
still does not start despite the
inlet being open and the
container filled, contact HYDAC
Service.
OLSW
en(us)
Page 40 / 76
BeWa OLSW 4268435 en-us 2017-11-09.docx
2017-11-09