background image

TM

If you smell gas

Discontinue use until the gas leak is discovered and 
corrected or the unit is replaced.
Check the regulator and its connections using soapy 
water. Tighten if necessary.
Check the hose connection to the unit using soapy 
water (this connection does not require Teflon tape, 
it  seals  with  a  flare  fitting).  If  there  is  a  gas  leak 
coming from the hose connection try to tighten but 
use a backup wrench and don’t over tighten. If there 
is still a leak at the hose connection remove the hose 
and inspect the brass gas inlet, it should be smooth 
with no nicks or gouges and should be clean. If there 
is a problem with this adapter either clean it off if it 
is dirty or contact Hydro Innovations for a replace-
ment adapter.
Check the gas adapter that comes installed on the
unit  with  soapy  water.  If  there  is  a  leak  at  this 
connection  use  a  backup  wrench  on  the  unit  and 
remove  the  gas  adapter.  Clean  the  threads  of  any 
sealant and reattach using Teflon tape. Do not over 
tighten.
If no external leaks were detected using soapy water 
and the smell of gas is coming from inside the unit 
do not use and contact Hydro Innovations.
 

If you have water dripping out of the bottom of 

the unit

Most  likely  you  are  experiencing  condensation 
dripping from the copper tubing inside the unit. This 
is caused by incoming water temperatures being too 
low, humidity in your garden being too high, or a 
combination of both. This is similar to a cold glass of 
water sweating and happens when the water cools 
the  tubing  below  the  dew  point  in  the  room.  We 
don’t have control over the humidity in your garden 
or your water temperature we do not cover damage 
to the unit caused by condensation The water must 
be warmed to above the dew point or the humidity 
must  be  lowered  in  the  garden  which  lowers  the 
dew point to below the water temperature.
If  using  a  recirculation  system  turn  up  the  chiller 
slowly until the condensations stops.
For drain to waste cooling the water can be stored in 
a  reservoir  and  allowed  to  warm  up  to  room 
temperature;  you  would  use  a  pump  to  supply 
water to the MiniGEN and the water would still be 
drained to waste.

 Troubleshooting Guide

The  incoming  water  for  the  MiniGEN  can  be  run 
through  our  Ice  Box  heat  exchanger  with  a  fan 
attached. The exiting water from the Ice Box should 
be connected to the inlet of the MiniGEN. With the 
fan  running  and  the  water  flowing  heat  from  the 
grow room will slightly warm the water that is used 
to  cool  the  MiniGEN  typically  raising  it  above  the 
dew point. As an added bonus cold air is blown in to 
your garden. This will typically cause the Ice Box to 
sweat which does not cause any damage and this 
water can be collected and removed from your grow 
room bringing down humidity levels.
If using drain to waste the cooling the user can be 
switch to a recirculation system to completely stop 
condensation. 
Check and tighten hose barb connections.
 

MiniGEN  does  not  try  to  light  or  relight,  no 

clicking is heard.

Check to make sure there is not air in the gas hose. 
After changing the bottle or after installation, you 
may need to cycle the unit on and off a few times 
before the air expelled.
Check to make sure that the unit is plugged in and 
that the outlet has power.
Check to make sure that the power cord is securely 
attached to the unit.
Check  for  gas  leaks,  there  is  a  sensor  that  detects 
internal gas leaks and if a leak is detected the unit 
will not run. Turn the unit off and smell for gas, if 
you smell gas coming from inside the unit, discon-
tinue use and contact Hydro Innovations.
Check to make sure that the propane bottle valve is on.
Check  bottle  level,  keep  in  mind  bottles  feel  heavy 
even when empty.
Check for kinks in the gas line
Check  to  make  sure  that  the  unit  does  not  have 
direct airflow from a fan. Too much airflow around 
the unit can cause the flame to blow out.
Make sure the unit is level in both directions, there is 
an out of level sensor that turns off the gas valve.



Reviews: