16
Page
Vent
for two-pipe
4" stainless
steel vent
straight pipe
Exhaust vent
collar (Female)
Intake vent collar
(Female)
4" stainless
steel vent
straight pipe
Exhaust vent
collar (Female)
4" stainless
steel vent
straight pipe
Intake vent
collar
(Female)
4" elbow
with bird
screen
1. Connect a 4" stainless steel vent
straight pipes directly on the
exhaust vent collar of the
micro-boiler.
2. Connect a 4" elbow directly
on the intake vent collar of the
micro-boiler.
1. Connect 4" stainless steel vent
straight pipes directly on the
exhaust/intake vent collar of the
micro-boiler.
For details of the op
tional
items, refer to the Installa
tion
manual for each Op
tional
item.
-Exhaust vent (Stainless steel vent)-
This is a Category IV appliance and must be vented accordingly. The vent system mus
t be sealed airtig
ht.
All seams and joints
without gaskets
must be sealed with high heat resistant silicone sealant or UL listed
aluminum adhesive tape having a minimum temperature ra
ting of 160 °F
. For best results, a vent system
should be as short and straight as possible.
•
The micro-boiler is a Category IV appliance and must be vented accordingly with any 4 inch vent
approved for use with Category III/IV or Special BH type gas vent.
•
The manufacturer recommends the NovaVent (Z-Vent) line
. However, the following are also UL
listed manufacturers: ProTech Systems Inc. (FasNSeal), Metal-Fab Inc., and Heat-Fab Inc. (Saf-T
Vent).
•
Follow the vent pipe manufacturer’s ins
tructions
when installing the vent pipe.
•
The maximum length of exhaust vent piping must not exceed
100
ft
.
(30
.5 m)
(deducting
5
ft
. (1.5
m) for each elbow used in the ven
ting
system). Do not use more than 5 elbows.
•
When the horizontal vent run exceeds 5
ft
. (1.5 m), support the vent run at 3
ft
.
(0
.9 m) intervals
with overhead hangers.
Diameter
Max. No. of Elbows Max. V
erti
cal and Horizontal (Total) Vent Length
4 in.
(102
mm)
5
100
ft
.
(30
.5 m )
*For each elbow added, deduct 5
ft.
(1.5 m) from max. vent length.
No. of Elbows
Max. V
erti
cal or Horizontal Vent Length
0
100
ft
.
(30
.5 m)
1
95
ft
. (29.
0
m)
2
90
ft
. (27.4 m)
3
85
ft
. (25.9 m)
4
80
ft
. (24.4 m)
5
75
ft
. (22.9 m)
Excludes vent terminators, termina
tion
elbows, or rain caps.
Vent
for single pipe