22
Page
-Measuring inlet gas pressure-
The micro-boiler cannot perform properly without su
fficie
nt inlet gas pressure. Below are ins
tructions
on
how to check the inlet gas pressure.
THIS IS ONLY TO BE DONE BY A LICENSED PROFESSIONAL
.
WATER CONNECTIONS
All pipes, pipe
fittings,
valves and other components, including soldering materials, must be suitable for
space heating
systems.
1.
A manual shuto
ff
valve must be installed on the cold water inlet to the micro-boiler between the main
water supply line and the micro-boiler.
2.
In
addition,
a manual shuto
ff
valve is also recommended on the hot water outlet of the micro-boiler.
If the micro-boiler is installed within, or subjected to, a closed loop water system, a thermal expansion
tank or code approved device to handle thermal expansion must be installed. We recommend isola
tion
valve sets with hose bibs for serviceability such as
flushi
ng. See maintenance and service
section
.
1. Turn o
ff
all electric power to the micro-boiler if service is to be performed.
2. Turn the manual gas valve located on the outside of the micro-boiler clockwise
to the o
ff
posi
tion
.
•
Do not use this micro-boiler if any part has been submersed under water.
Immediately call a licensed professional to inspect the micro-boiler to replace
any damaged parts.
•
Do not reverse the hot outlet and cold inlet c
onnectio
ns to the micro-boiler.
This will not properly
acti
vate the micro-boiler.
CAUTION
1. Shut o
ff
the manual gas valve on the gas supply line.
2. Remove the screw for the pressure port located on the
gas inlet of the micro-boiler shown in the diagram on
the right.
3. Connect the manometer to the pressure port.
4. Re-open the manual gas valve. Check to see that there
are no gas leaks. Take a reading of the gas pressure.
Open some of the
fi
xtures that use the highest
fl
ow rate
to turn on the micro-boiler.
5. Check the inlet gas pressure. Take another reading.
When the micro-boiler is on maximum and minimum
burn, the manometer should read from 5.0” to 10.5”
W.C. (1.24 to 2.61 kPa) for Natural gas, or from 8.0” to
14.0” W.C. (1.99 to 3.48 kPa) for Propane. Verify that the
pressure drop is acceptable.
3.
Before installing the micro-boiler,
flush
the system to remove all debris, and
a
ft
er installa
tion
is complete, purge
the air from the line. Failure to do so
may cause damage to the boiler.
Cold
inlet
Hot
outlet
Gas inlet
As Close as
Possible
Pressure relief valve
Pressure port
Summary of Contents for HS120CON-LP
Page 27: ......