Hydrological Services Pty Ltd
Data Logger Model ML1-420
©
Copyright
ML1-420 100-10
Issue 1.00 6 Apr, 2011
3.2.4 Communications
The MiniLog ML1-420 has an RS232 serial interface to support asynchronous ASCII
communications to accommodate data extraction and user set-up. This port operates at 1200,
2400, 4800, 9600, 19200, 38400 and 57600 baud with 8 data bits, no parity and 1 stop bit.
If initially you can’t establish communications with the ML1-420, try each of the 7 baud
rates, in case it has been changed from the default rate of 9600.
Each digital input event, and 4-20mA measurement that is logged is also transmitted on the
serial port, unless the event output flag is off (EV=off).
The RS232 serial port interface may be connected to a modem for remote interrogation and
data retrieval – see Appendix A for more details.