Page 21
5.5 Steam line and condensate
hose layout
Because of the high requirements on hose
material under the operating conditions
given, it is recommended to use genuine
HygroMatik hoses only.
5.5.1 Guide lines for steam line
design
•
Steam hose nominal diameter must not
be smaller than the steam outlet of the
HygroMatik steam humidifier (do not
restrict the cross-section, otherwise
back pressure will increase)
•
Steam hoses must be laid without sags
and kinks and with a continuous slope
of 5-10% (otherwise sags may result).
•
Steam hoses must be supported every
500 mm (20 inches) by clamp brackets
•
Steam hoses should be kept as short
as possible. Implement lengths be-
yond 5 m (16 ft.) as insulated fixed pip-
ing to keep energy loss and conden-
sate generation to a minimum. Beyond
10 m (32 ft.) insulated installation is a
must. Fixed piping is generally recom-
mended for straight steam line seg-
ments
•
When 2 steam manifolds are in use
(other than with a standard implemen-
tation), place steam Y piece as close as
possible to the steam manifolds. Such,
for the main part of the piping just one
steam hose is required and condensate
loss is minimized
•
Allow easy access to the steam pipe/
steam hose installation
•
Pressure conditions within the duct are
influenced by device steam output, steam
line layout and the duct composition itself.
In some rare situations it may become
necessary to optimize steam line layout
for achieving the results intended
•
Respect minimum bending radii:
DN 25 Steam hose: Rmin = 200 mm/8“
DN 40 Steam hose: Rmin = 400 mm/16“
5.5.2 Condensate hose layout
(only for electrode steam humidifiers)
The condensate hose may be run from the
steam manifold back to the steam cylinder,
as depicted in the schematic drawing below
with concern to installation type 1. Alterna-
tively, the condensate hose may be fed
directly in a wastewater pipe or a drain (s.
installation type 2).
Should condensate return into the steam cyl-
inder be intended, the connection stub on the
cylinder upper part must be drilled out first
with a ANSI drill size „O“ drill. To do so, the
steam cylinder must be removed from the
housing (s. maintenance chapter, section
„Steam cylinder removal and reinstallation“).
In case of a console instead of a housing, the
cylinder is to be lifted off the cylinder base for
drilling the stub or may even remain in place.
For heater element humidifiers:
If condensate return is necessary, please
contact the HygroMatik hotline.
Please note
Please note
with an 8 mm (ANSI drill size „O“) drill,
Drill out condensate hose connection stub
Steam cylinder top view
if required
Summary of Contents for FlexLine FLH03
Page 1: ...FlexLine Electric Heater Steam Humidifiers ÁFLH ENKÈ FLH EN E 8881164 Manual ...
Page 45: ...Page 45 11 Declaration of Conformity ...
Page 49: ...Page 49 This page intentionally left blank ...
Page 50: ...Page 50 This page intentionally left blank ...