7. Electrical connection
Risk of electrical shock!
Hazardous electrical voltage.
All work related to electrical installation to be
performed by expert staff (electricians or
expert personnel with equivalent training)
only.
Do not connect the reverse osmosis unit
to the live power supply before all installation
work has been completed
The customer is responsible for checking
expert staff qualification.
.
General installation rules
•
All local rules concerning the imple-
mentation of electrical installations
must be obeyed
•
Electric connector cables to be laid pro-
fessionally
•
Install the electrical connections accor-
ding to the wiring diagram
•
With units of a nominal power output
> 33 kW electrical connection to a per-
manent line is mandatory (according to
VDE 0700 Part 98)
Possible electronical components de-
struction through electrostatical dischar-
ge!
Prior to commencing electrical installation
work, steps must be taken to guard the sen-
sitive electronical components of the unit con-
trol against damage from electrostatical
discharge.
7.1 Electrical installation
approach
»
Provide fuses with a contact gap of
at least 3mm per pole.
»
Install a separate main connection
for each steam cylinder including
main circuit breaker, main switch
etc. .
»
Make main connection according to
the table below.
Main connection and Fusing
For the FlexLine steam humidifiers in the
standard version, main connection can be
found in the Technical Data (in the chapter of
the same name)
.
Other operating voltages on request.
HygroMatik recommends the use of slow
blowing up to middle time-lag main fuses.
Steam humidifier installations should encor-
porate an individual residual current circuit
breaker (Type A-RCD).
The maximum current consumption and the
resulting required fuse protection of the indi-
vidual standard unit types can be found in the
technical data table (chapter Technical data
at the end of this manual).
WARNING
!
Please note