Page 36
»
Clean both strainer.
»
Check the base and its connections
for limescale deposits and clean if
necessary.
»
Insert a new O-ring in the base.
»
Insert new O-rings between the cyl-
inder halves and in the steam hose
adapter.
»
Put the cylinder halves together and
reconnect them with the flange
clamps.
»
When assembling the cylinder, make
sure that the brackets and reinforce-
ments are on top of each other.
Risk of functional disruption!
Use descaler or cleaning detergents only for
cylinder and heater element cleaning. Do not
introduce in cylinder base or apply to hoses!
Prior to restarting the unit, make sure that the
device assemblies in question are thoroughly
flushed or rinsed.
Possible damage to the unit!
Excessive use of force during mechanical
cleaning of the cylinder or heating element
can damage these parts of the unit.
9.5.3 Cleaning the connecting hoses,
base connections, fine filter
and drain pump
»
Check the connection hoses for con-
dition and free passage.
»
Check all connections of the cylinder
base for free passage.
»
Clean the hoses and connections if
necessary.
»
Remove the fine filter on the water
connection side from the solenoid
valve and clean it under running
water.
»
Clean the drain pump as described
in the section of the same name.
When operating with partially softened water
or tap water, scale may be discharged with
the steam flow and may settle in the nozzle
positioned in steam hose adapter. Therefore,
this nozzle should be inspected regularly as
part of the general maintenance review and
cleaned if necessary.
NOTICE
NOTICE
NOTICE