HB-8000C Series
Sensor Operated Flush Valve
Control Module Settings
Flow rate and sensor arming time can be adjusted via the dip switches located on the Control Module.
Urinal
0.125*
ON
ON
OFF
ON
0.5
ON
ON
ON
ON
1.0
ON
ON
ON
OFF
Closet
1.28
ON
ON
OFF
OFF
1.6
ON
OFF
ON
ON
Flushing Volume
Flush Valves are preset to 1.0 GPF for urinal and 1.6 GPF for closet
Urinal
Standard
OFF
OFF
OFF
ON
3 seconds
Optional
ON
OFF
OFF
OFF
1.5 seconds
Sensor Arming Time
Sensing Time Required to Flush
Closet
Standard
ON
OFF
OFF
OFF
4 seconds
Optional
OFF
OFF
OFF
OFF
8 seconds
NOTE: PUSH THE RESET BUTTON ON THE CONTROL MODULE AFTER
ANY ADJUSTMENTS TO THE DIP SWITCHES.
Sensor Distance Adjustment
Clockwise Increase sensing distance
Counter-Clockwise Decrease sensing distance
*0.125 flow rate setting only available if ordered that way from the factory
For alternate flow rates not listed, please contact Hydrotek direct