13.8.7 Adiabate submenu
Table of parameters for the adiabate functions
15: Adiabatic
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
Min
Max
FS
[ ] refers to a related explanation of the term
1 Flush_hygiene
Flush after waiting time and at the time specified in parameter 15/3.
1
2
2 Rinse_Hygiene_Time
00:00
23:59
00:00
Time setting for the execution of the hygiene flush
3 Flush_hygiene_waiting_time
1
2880
1440
Time in minutes to the next obligatory hygiene flush
4 Flush_duration
1
600
20
The duration of the flushing time in seconds (with pump pressure or line pressure
according to the setting made beforehand)
5 Relieve_Duration
1
240
5
Determines the duration of the pressure relief [85] in seconds.
6
Delay_reverse osmosis system
10
180
10
Delay between opening the inlet solenoid valve and starting the high-pressure
pump. Enables the pressure build-up in the reverse osmosis system.
7 Load_switchover_hysteresis
0,5
5,0
1,0
Hysteresis in % for the changeover points
8 Load_switch_wait
1
10
3
Waiting time in seconds before a load changeover triggered by the request
becomes active (to prevent oscillation at the changeover point)
Selection
Waiting time
Time_of_day
Adjustment/value range
Factory setting (FS) Bold