15.2.4.2 Setting of the optional by-
pass valve on the distribu-
tion manifold
Method
»
Apply control signal
≥
1.5 V
-> unit starts operation.
»
Reduce control signal to approx. 1 V
-> pressure sinks to 25 bar.
»
Unfasten headless Allan screw (2)
on by-pass valve (3) and adjust
valve slowly until a frequency
between 9 and 12 Hz can be read in
the frequency converter display.
»
Fasten Allan screw again for secur-
ing the setting.
»
Return to the normal operation set-
tings should they have been
changed.