Page 61
13.8.3 Control submenu
Table of control parameters
05: Control
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
Min
Max
FS
[ ] refers to a related explanation of the term
1 Control_settings
Combinations of control type and input signal type/range
2 Output_max.
25,0
100,0
100,0
The maximum output power [43] can be limited to between 25 and 100%
3
Δ
Power_limitation
0,0
50,0
0,0
Reduction of the max. humidification output for the purpose of load shedding
[101].
4 Output_signal
Mapping of the output signal [69] to an internal value
0 No
mapping
1
Output signal is proportional to the demand [5] from the external controller [73]
2
Output signal is proportional to the internal actuator signal [42]
3
Output signal is proportional to the actual humidity value [1]
17 Humidity_set_value
0,0
99,0
50,0
Set value [3] of RH [2] in %
20 PI-controller_gain
0,5
100,0
5,0
Proportional part of PI controller
21 PI-controller_integral
0
100
10
Integral part of PI controller
22 Humidity_notification
5,0
99,0
50,0
When the set humidity [%] has been reached, one of the relays is energised,
which must have been assigned code 211 (humidity reached) for this purpose
23 Humidity_set_max
5,0
99,0
80,0
Specification of max. humidity for the switch-off point when using the floating
max. limiter [35]
24 Pi-controller_max_gain
0,5
100,0
5,0
Amplification of 2nd PI controller when using the floating max. limiter [35]
33 Damping_analog
inputs
The attenuation for capacitive sensors is activated. Only possible with activated PI
controller
0
Switch off attenuation
1
Switch on attenuation
Adjustment/value range
Control_sig._internal
Humidity_actual_value
Selection
Off
On
Factory setting (FS) Bold
Selection
see: 01-4 Control_settings
Selection
Off
Control_sig._external