15.1.6 Cleaning the spray system
The spray system should be checked for con-
tamination and damage every 4 weeks. Any
contaminants must be removed with a alka-
line-based cleaning agent basis that meets
the VDI 6022 requirements. The spray sys-
tem should be thoroughly cleaned at least
once a year.
15.1.7 Cleaning the mounting pro-
files
The mounting profiles of the spray system
and the aerosol separators should be
reviewed as a part of the annual mainte-
nance for contamination or damage. Possible
impurities must be removed with a cleaning
agent.
15.1.8 Cleaning the humidification
chamber
»
Clean the humidification chamber
and the base tray as required with
the cleaning agent that is recom-
mended by the manufacturer of the
humidification chamber.
»
After cleaning, rinse and let dry.
Risk of material damage!
When cleaning the spray system, do not aim
the water jet at the aerosol separators. Any
upstream or downstream heating or cooling
units must not become wet during cleaning.