1.3.2 General Symbols
This symbol is used whenever a situation
requires special attention beyond the scope
of safety instructions.
1.4 Intended Use
The high-pressure nozzle system is used for
air humidification and cooling with desali-
nated water having a conductivity of 5-50
µS/cm.
Proper use includes fulfilment of the assem-
bly, disassembly, reassembly, start-up, oper-
ating and maintenance conditions specified
by us as well as disposal measures.
Only qualified and personnel may work on or
with the system (a supplementary qualifica-
tion according to VDI 6022 Part B or an
equivalent qualification is recommended).
Persons transporting or working on or with
the system must have read and understood
the relevant parts of this operating manual,
particularly the 'Safety instructions' section.
Staff must also be informed of possible haz-
ards by the opera-ting company. Please keep
a copy of the operating manual at the loca-
tion where the device is being used.
Applications:
The high-pressure nozzle system has a wide
range of applications.These systems are
used wherever low-energy adiabatic humidifi-
cation or cooling or systems with high-preci-
sion control are needed. They can be found
in such places as offices, storerooms, pro-
duction halls, clean rooms, hospitals and
concert halls.
Components installed in ventilation and air-
conditioning systems must be suitable for the
intended use; i.e. they must be corrosion-
resistant according to VDI 6022 or equiva-
lent, easy to clean, accessible and hygienic.
Furthermore, they must not facilitate growth
of microorganisms.
Improper use:
Any other use not compatible with the
intended use outlined above is not allowable.
Improper use as well as changes in hardware
or software that are not authorized by Hygro-
Matik will lead to the total loss of guarantee
and warranty claims.
Operating conditions must be met at any
time!
•
The nozzle system is not frost-proofed
and not suitable for outdoor installation
•
The room temperature should lie
between 5 and 40 °C
•
When attempting to operate the system
in a position higher than 1000 m above
sea level, pls. talk to HygroMatik prior
to installation
•
The pressure level of the nozzle sys-
tem must not be changed without the
consent of HygroMatik GmbH
•
The nozzle system must not be used
for cold water cooling without the con-
sent of HygroMatik GmbH
•
The nozzle system must not be oper-
ated with a vertical flow without the
consent of HygroMatik GmbH
For hygienic reasons (legionella prevention),
the feed water temperature should not
exceed 15 °C.