Page 26
When pressing the
NEXT
after the step prior to the current one ,
setting the forced regeneration parameter is enabled:
»
Use the
Δ
and
∇
arrow keys for setting the days or
leave the setting unchanged, if appropriate
»
Press the
NEXT
key for saving and preparing the input
of the next parameter (forced regeneration time of day
setting)
Setting time of the day for forced regeneration
Factory setting for forced regeneration time is 2.00 a.m..- a time
of day when typically no demand for water by a consumer
exists.. When pressing the
NEXT
key in the step prior to the cur-
rent one, input of time of day was enabled:
»
Use the
Δ
and
∇
arrow keys for setting the time of day
or leave the setting unchanged, if appropriate
»
Press the
NEXT
key for saving and exiting input mode
Beenden der Programmierung
By pressing the
NEXT
key in the step described above, pro-
gramming of the control valve was finished and the display
returned to normal „Time“ mode.
Changing the factory settings of further parameters
Settings beyond the basic settings described here may be made
by service personnel. For that porpuse, a dedicates program-
mining manual is available from Hygromatik.
6.5 Setting of the optional external blending-
valve
Please note:
When using the optionally available external
mounting block (Mounting block with integrated blending valve,
art. no. E-5000072 ), pls follow the recommendations given in
the operating instructions leaflet provided with the article.
Please note:
For operating HygroMatik steam humidifiers, a
mixed water hardness of 4 °dH is recommended for electrode
humidifiers. For operating heater humidifiers pls. contact Hygro-
Matik first.
In case of an inverted osmosis device downstream of a Water-
Line ion exchange softener, zero-degree soft water is required.
Such, no raw water is blended to the soft water.