Page 6
iron (Fe) content limit is 0.2 mg/l, max. manganese (Mn) is
0.05 mg/l
•
For use with raw water with a
iron and/or manganese
content exceeding these limits, only HygroMatik WaterLine
softeners of the WL-DP family type are suited
•
The softener device must
not be operated outside
in the
exterior
•
Frost protection
and
humidity protection
must be ensu-
red
•
Allowable
environmental temperature
is 5 - 40 °C with a
max. r.h. of 60 percent
•
Use of a
system separator
according to EN 1717 (former
DIN 1998, part 4) is obligatory
•
Optimum
flow pressure
of teh device is 4.0 bar
Please note
: For protection of the softener device, a
water fil-
ter
according to DIN 13443-1 implemented in front of the water
intake is obligatory. Without such a filter the ion exchanger resin
might silt-up within short periods of time. Also, the control valve
might get damaged by dirt ingress.
1.2 Typographic markings
•
lists with items beginning with bullets: general lists
»
lists with items beginning with arrows: work or operating
steps which should or must be carried out in the speci-
fied order
installation steps which must be checked
italics
figure and plan names
1.3 Documentation
Storage
Please keep this operating manual in a safe place where it is
accessible at all times. If you sell the product, be sure to include
this manual. Please contact HygroMatik if the documentation is
lost.
Language versions
This operating manual is available in different languages. Please
contact your HygroMatik dealer or HygroMatik for details.
Summary of Contents for WaterLine Double
Page 43: ...Page 43 This page intentionally left blank ...
Page 44: ......